Assessment Year 2012
Principal Product metallic fittings
NAICS 332919: Other Metal Valve and Pipe Fitting Manufacturing
SIC 3494: Valves and Pipe Fittings, Not Elsewhere Classified
Sales Range $10
M
to 50
M
# of Employees 72
Plant Area 100,000
ft2
Annual Production 100,000
lb
Production Hrs. Annual 6,240
hrs
Location (State) Michigan

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $125,363 1,505,400
kWh
Electricity Demand $35,502 3,970
kW-mo/yr
Natural Gas $43,334 6,526
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $14,830 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $6,438

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings
01 2.4235: Remove or close off unneeded compressed air lines $3,930 $1,000 $3,930
47,179
kWh
-
02 2.4221: Install compressor air intakes in coolest locations $3,595 $1,000 $3,595
43,160
kWh
-
03 2.7142: Utilize higher efficiency lamps and/or ballasts $2,508 $2,500 $2,079
24,960
kWh
$429
-
kW-mo/yr
04 2.4231: Reduce the pressure of compressed air to the minimum required $2,256 $200 $2,256
27,955
kWh
-
05 2.6212: Turn off equipment during breaks, reduce operating time $1,975 $1,500 $1,637
19,656
kWh
$338
-
kW-mo/yr
06 2.6211: Conserve energy by efficient use of vending machines $566 $100 $566
6,800
kWh
-
TOTAL RECOMMENDED $14,830 $6,300 $14,063
169,710
kWh
$767
-
kW-mo/yr
TOTAL IMPLEMENTED $6,438 $3,500 $6,009
72,139
kWh
$429
-
kW-mo/yr
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs