Assessment Year | 2012 |
---|---|
Principal Product | steel coils |
NAICS | 336370: Motor Vehicle Metal Stamping |
SIC | 3465: Automotive Stampings |
Sales Range | $50 M to 100M |
# of Employees | 107 |
Plant Area |
200,000
ft2
|
Annual Production | 40,000
ton
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Michigan |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $240,365 | 3,435,825 |
kWh
|
$0.070 |
Electricity Demand | $112,764 | 9,524 |
kW-mo/yr
|
$11.84 |
Natural Gas | $42,033 | 5,043 |
MMBtu
|
$8.33 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $30,446 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $15,433 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4324: Replace hydraulic / pneumatic equipment with electric equipment | $13,566 | $16,700 |
$14,241
203,445
kWh
|
$(-675.0)
-
kW-mo/yr
|
- | - | |
02 | 2.3132: Recharge batteries on during off-peak demand periods | $10,324 | $2,000 | - | - | $10,324 | - | |
03 | 2.4221: Install compressor air intakes in coolest locations | $2,021 | $1,500 |
$2,021
28,875
kWh
|
- | - | - | |
04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,447 | $200 |
$1,447
20,685
kWh
|
- | - | - | |
05 | 2.6211: Conserve energy by efficient use of vending machines | $595 | $100 |
$595
8,500
kWh
|
- | - | - | |
06 | 2.7291: Reschedule and rearrange multiple-source heating systems | $1,364 | - | - | - | - |
$1,364
-
MMBtu
|
|
07 | 2.7221: Lower temperature during the winter season and vice-versa | $1,129 | $1,000 | - | - | - |
$1,129
-
MMBtu
|
|
TOTAL RECOMMENDED | $30,446 | $21,500 |
$18,304
261,505
kWh
|
$(-675.0)
-
kW-mo/yr
|
$10,324 |
$2,493
-
MMBtu
|
||
TOTAL IMPLEMENTED | $15,433 | $4,600 |
$2,616
37,375
kWh
|
- | $10,324 |
$2,493
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs