Assessment Year | 2011 |
---|---|
Principal Product | Polyolephin Resins |
NAICS | 325211: Plastics Material and Resin Manufacturing |
SIC | 2821: Plastics Materials, Synthetic Resins, and Nonvulcanizable Elastomers |
Sales Range | $50 M to 100M |
# of Employees | 93 |
Plant Area |
185,000
ft2
|
Annual Production | 41,000,000
lb
|
Production Hrs. Annual | 6,000
hrs
|
Location (State) | Michigan |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $503,419 | 8,133,840 |
kWh
|
$0.062 |
Electricity Demand | $244,807 | 14,622 |
kW-mo/yr
|
$16.74 |
Natural Gas | $41,245 | 5,651 |
MMBtu
|
$7.30 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $31,881 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $5,546 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|
01 | 2.7135: Install occupancy sensors | $3,851 | $2,100 |
$3,851
57,837
kWh
|
- | - | |
02 | 2.4224: Upgrade controls on compressors | $2,043 | $3,615 |
$2,043
33,000
kWh
|
- | - | |
03 | 2.4221: Install compressor air intakes in coolest locations | $1,167 | $1,000 |
$1,167
18,848
kWh
|
- | - | |
04 | 2.7491: Insulate glazing, walls, ceilings, and roofs | $2,885 | $18,495 | - |
$2,885
-
MMBtu
|
- | |
05 | 2.7447: Install vinyl strip / high speed / air curtain doors | $2,336 | $2,471 | - |
$2,336
-
MMBtu
|
- | |
06 | 2.2437: Recover waste heat from equipment | $2,285 | $1,000 | - |
$2,285
-
MMBtu
|
- | |
07 | 2.8114: Change rate schedules or other changes in utility service | $982 | $10 | - | - | $982 | |
08 | 2.2492: Use "heat wheel" or other heat exchanger to cross-exchange building exhaust air with make-up air | $16,332 | $92,500 | - |
$16,332
-
MMBtu
|
- | |
TOTAL RECOMMENDED | $31,881 | $121,191 |
$7,061
109,685
kWh
|
$23,838
-
MMBtu
|
$982 | ||
TOTAL IMPLEMENTED | $5,546 | $7,086 |
$3,210
51,848
kWh
|
$2,336
-
MMBtu
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs