Assessment Year | 2008 |
---|---|
Principal Product | Interior Automotive Trim |
NAICS | 336390: Other Motor Vehicle Parts Manufacturing |
SIC | 3714: Motor Vehicle Parts and Accessories |
Sales Range | $100 M to 500M |
# of Employees | 220 |
Plant Area |
160,000
ft2
|
Annual Production | 1,217,000
pieces
|
Production Hrs. Annual | 5,880
hrs
|
Location (State) | Michigan |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $107,972 | 2,145,427 |
kWh
|
$0.050 |
Electricity Demand | $46,109 | 4,596 |
kW-mo/yr
|
$10.03 |
Natural Gas | $43,568 | 3,815 |
MMBtu
|
$11.42 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $27,709 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.7221: Lower temperature during the winter season and vice-versa | $10,849 | $500 | - | - |
$10,849
-
MMBtu
|
|
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,423 | $19,322 |
$4,522
90,418
kWh
|
$901
-
kW-mo/yr
|
- | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,497 | - |
$1,782
35,640
kWh
|
$715
-
kW-mo/yr
|
- | |
04 | 2.3132: Recharge batteries on during off-peak demand periods | $2,161 | $3,500 | - |
$2,161
-
kW-mo/yr
|
- | |
05 | 2.4221: Install compressor air intakes in coolest locations | $1,880 | $515 |
$1,432
19,626
kWh
|
$448
-
kW-mo/yr
|
- | |
06 | 2.7135: Install occupancy sensors | $1,706 | $2,484 |
$1,706
58,435
kWh
|
- | - | |
07 | 2.6218: Turn off equipment when not in use | $1,361 | $580 |
$1,361
26,415
kWh
|
- | - | |
08 | 2.7221: Lower temperature during the winter season and vice-versa | $1,284 | - |
$652
13,051
kWh
|
$632
-
kW-mo/yr
|
- | |
09 | 2.7224: Reduce space conditioning during non-working hours | $548 | $280 | - | - |
$548
-
MMBtu
|
|
TOTAL RECOMMENDED | $27,709 | $27,181 |
$11,455
243,585
kWh
|
$4,857
-
kW-mo/yr
|
$11,397
-
MMBtu
|
||
TOTAL IMPLEMENTED | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs