| Assessment Year | 2007 |
|---|---|
| Principal Product | Sippable Soup and Gravy |
| NAICS | 311422: Specialty Canning |
| SIC | 2032: Canned Specialties |
| Sales Range | $10 M to 50M |
| # of Employees | 150 |
| Plant Area |
103,000
ft2
|
| Annual Production | 10,400,000
pieces
|
| Production Hrs. Annual | 4,250
hrs
|
| Location (State) | Michigan |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $523,091 | 7,653,600 |
kWh
|
$0.068 |
| Electricity Demand | $135,251 | 14,780 |
kW-mo/yr
|
$9.15 |
| Electricity Fees | $8,109 | - |
|
- |
| Natural Gas | $1,216,937 | 105,013 |
MMBtu
|
$11.59 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $40,483 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $29,628 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.1233: Analyze flue gas for proper air/fuel ratio | $9,540 | $14,000 | - | - |
$9,540
-
MMBtu
|
|
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $8,573 | $7,025 |
$6,298
92,145
kWh
|
$2,275
-
kW-mo/yr
|
- | |
| 03 | 2.7111: Reduce illumination to minimum necessary levels | $8,279 | - |
$6,531
95,550
kWh
|
$1,748
-
kW-mo/yr
|
- | |
| 04 | 2.4239: Eliminate or reduce compressed air usage | $7,947 | $4,500 |
$5,767
84,379
kWh
|
$2,180
-
kW-mo/yr
|
- | |
| 05 | 2.4221: Install compressor air intakes in coolest locations | $2,647 | $120 |
$1,921
28,103
kWh
|
$726
-
kW-mo/yr
|
- | |
| 06 | 2.2414: Use waste heat from hot flue gases to preheat | $1,516 | $1,650 | - | - |
$1,516
-
MMBtu
|
|
| 07 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,215 | $75 |
$881
12,892
kWh
|
$334
-
kW-mo/yr
|
- | |
| 08 | 2.2511: Insulate bare equipment | $766 | $454 | - | - |
$766
-
MMBtu
|
|
| TOTAL RECOMMENDED | $40,483 | $27,824 |
$21,398
313,069
kWh
|
$7,263
-
kW-mo/yr
|
$11,822
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $29,628 | $18,695 |
$15,100
220,924
kWh
|
$4,988
-
kW-mo/yr
|
$9,540
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs