| Assessment Year | 2006 |
|---|---|
| Principal Product | Powder Coating |
| NAICS | 332813: Electroplating, Plating, Polishing, Anodizing, and Coloring |
| SIC | 3471: Electroplating, Plating, Polishing, Anodizing, and Coloring |
| Sales Range | $1 M to 5M |
| # of Employees | 30 |
| Plant Area |
37,000
ft2
|
| Annual Production | 0
units
|
| Production Hrs. Annual | 4,420
hrs
|
| Location (State) | Ohio |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $23,350 | 327,654 |
kWh
|
$0.071 |
| Electricity Demand | $6,252 | 544 |
kW-mo/yr
|
$11.49 |
| Electricity Fees | $393 | - |
|
- |
| Natural Gas | $142,808 | 13,048 |
MMBtu
|
$10.94 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $10,878 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $7,204 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|
| 01 | 2.1133: Adjust burners for efficient operation | $3,769 | $500 | - |
$3,769
-
MMBtu
|
|
| 02 | 2.7314: Reduce ventilation air | $2,507 | $500 | - |
$2,507
-
MMBtu
|
|
| 03 | 2.2414: Use waste heat from hot flue gases to preheat | $2,070 | $1,250 | - |
$2,070
-
MMBtu
|
|
| 04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,462 | $3,479 |
$1,462
15,886
kWh
|
- | |
| 05 | 2.2531: Re-size charging openings or add movable cover or door | $536 | $300 | - |
$536
-
MMBtu
|
|
| 06 | 2.4221: Install compressor air intakes in coolest locations | $392 | $1,000 |
$392
4,256
kWh
|
- | |
| 07 | 2.2511: Insulate bare equipment | $142 | $310 | - |
$142
-
MMBtu
|
|
| TOTAL RECOMMENDED | $10,878 | $7,339 |
$1,854
20,142
kWh
|
$9,024
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $7,204 | $2,300 |
$392
4,256
kWh
|
$6,812
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs