Assessment Year 2005
Principal Product Transmission and Steering Components
NAICS 336350: Motor Vehicle Transmission and Power Train Parts Manufacturing
SIC 3714: Motor Vehicle Parts and Accessories
Sales Range $10
M
to 50
M
# of Employees 128
Plant Area 48,000
ft2
Annual Production 20,000,000
pieces
Production Hrs. Annual 5,304
hrs
Location (State) Michigan

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $112,787 3,077,259
kWh
Electricity Demand $76,015 8,016
kW-mo/yr
Electricity Fees $3,524 -
Natural Gas $13,980 1,930
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $56,239 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $45,052

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Other Liquid (non-haz) Savings
01 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $32,977 $1,275 $20,653
563,521
kWh
$12,324
-
kW-mo/yr
- -
02 3.6193: Install equipment (eg compactor) to reduce disposal costs $9,488 $11,000 - - - $9,488
-
gal
03 2.2437: Recover waste heat from equipment $7,059 $1,000 - - $7,059
-
MMBtu
-
04 2.7142: Utilize higher efficiency lamps and/or ballasts $3,062 $4,152 $1,972
53,801
kWh
$1,090
-
kW-mo/yr
- -
05 2.4221: Install compressor air intakes in coolest locations $1,954 $2,000 $1,226
33,443
kWh
$728
-
kW-mo/yr
- -
06 2.7124: Make a practice of turning off lights when not needed $1,360 - $1,360
37,102
kWh
- - -
07 2.4239: Eliminate or reduce compressed air usage $339 $1,000 $83
2,274
kWh
$256
-
kW-mo/yr
- -
TOTAL RECOMMENDED $56,239 $20,427 $25,294
690,141
kWh
$14,398
-
kW-mo/yr
$7,059
-
MMBtu
$9,488
-
gal
TOTAL IMPLEMENTED $45,052 $8,427 $23,851
650,765
kWh
$14,142
-
kW-mo/yr
$7,059
-
MMBtu
-
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Other Liquid (non-haz) Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs