Assessment Year | 1997 |
---|---|
Principal Product | Potato Products |
NAICS |
n/a
|
SIC | 2037: Frozen Fruits, Fruit Juices, and Vegetables |
Sales Range | $10 M to 50M |
# of Employees | 220 |
Plant Area |
214,307
ft2
|
Annual Production | 114,000,000
lb
|
Production Hrs. Annual | 7,056
hrs
|
Location (State) | Michigan |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $624,095 | 17,648,887 |
kWh
|
$0.035 |
Electricity Demand | $84,811 | 36,084 |
kW-mo/yr
|
$2.35 |
Electricity Fees | $145,562 | - |
|
- |
Natural Gas | $601,098 | 196,529 |
MMBtu
|
$3.06 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $297,606 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings | Primary Product Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.4133: Use most efficient type of electric motors | $4,141 | $4,497 |
$2,276
77,081
kWh
|
$1,865
-
kW-mo/yr
|
- | - | - | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $6,616 | $29,553 |
$3,927
145,369
kWh
|
$2,689
-
kW-mo/yr
|
- | - | - | |
03 | 2.4221: Install compressor air intakes in coolest locations | $696 | $1,000 |
$382
12,896
kWh
|
$314
-
kW-mo/yr
|
- | - | - | |
04 | 2.2523: Reduce infiltration to refrigerated areas; isolate hot equipment from refrigerated areas | $35,249 | $8,500 |
$25,096
760,844
kWh
|
$10,153
-
kW-mo/yr
|
- | - | - | |
05 | 2.2511: Insulate bare equipment | $1,392 | $5,361 | - | - |
$1,392
-
MMBtu
|
- | - | |
06 | 3.6112: Use filter and drying oven to reduce sludge volume | $245,000 | $10,000 | - | - | - | $245,000 | - | |
07 | 4.652: Replace existing equipment with more suitable substitutes | $4,512 | $300 | - | - | - | - | $4,512 | |
TOTAL RECOMMENDED | $297,606 | $59,211 |
$31,681
996,190
kWh
|
$15,021
-
kW-mo/yr
|
$1,392
-
MMBtu
|
$245,000 | $4,512 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings | Primary Product Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs