| Assessment Year | 1997 |
|---|---|
| Principal Product | Envelopes |
| NAICS |
n/a
|
| SIC | 2699: |
| Sales Range | $10 M to 50M |
| # of Employees | 115 |
| Plant Area |
45,000
ft2
|
| Annual Production | 700,000,000
pieces
|
| Production Hrs. Annual | 7,488
hrs
|
| Location (State) | Michigan |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $85,432 | 2,886,284 |
kWh
|
$0.030 |
| Electricity Demand | $112,262 | 6,576 |
kW-mo/yr
|
$17.07 |
| Electricity Fees | $(-2,665.0) | - |
|
- |
| Natural Gas | $4,371 | 1,009 |
MMBtu
|
$4.33 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $35,385 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $30,581 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Other Liquid (haz) Savings | Administrative Changes Savings | Primary Raw Material Savings | Primary Product Savings |
|---|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.4133: Use most efficient type of electric motors | $12,562 | $7,260 |
$8,751
167,057
kWh
|
$3,811
-
kW-mo/yr
|
- | - | - | - | |
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $12,062 | $24,775 |
$7,915
127,491
kWh
|
$4,147
-
kW-mo/yr
|
- | - | - | - | |
| 03 | 2.4221: Install compressor air intakes in coolest locations | $1,078 | $1,200 |
$751
14,361
kWh
|
$327
-
kW-mo/yr
|
- | - | - | - | |
| 04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $4,879 | - |
$4,708
89,683
kWh
|
$171
-
kW-mo/yr
|
- | - | - | - | |
| 05 | 3.8143: Recycle cleaning solvent and reuse | $2,412 | $7,200 | - | - |
$451
-
gal
|
$(-1,784.0) | $3,745 | - | |
| 06 | 4.121: Maintain clean conditions before painting | $2,392 | $5 | - | - | - | - | - | $2,392 | |
| TOTAL RECOMMENDED | $35,385 | $40,440 |
$22,125
398,592
kWh
|
$8,456
-
kW-mo/yr
|
$451
-
gal
|
$(-1,784.0) | $3,745 | $2,392 | ||
| TOTAL IMPLEMENTED | $30,581 | $33,235 |
$22,125
398,592
kWh
|
$8,456
-
kW-mo/yr
|
- | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Other Liquid (haz) Savings | Administrative Changes Savings | Primary Raw Material Savings | Primary Product Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs