Assessment Year | 1996 |
---|---|
Principal Product | Seamless Tubing |
NAICS |
n/a
|
SIC | 3498: Fabricated Pipe and Pipe Fittings |
Sales Range | $10 M to 50M |
# of Employees | 86 |
Plant Area |
109,000
ft2
|
Annual Production | 960
thousand feet
|
Production Hrs. Annual | 7,488
hrs
|
Location (State) | Michigan |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $101,248 | 3,361,665 |
kWh
|
$0.030 |
Electricity Demand | $112,293 | 6,274 |
kW-mo/yr
|
$17.90 |
Electricity Fees | $5,085 | - |
|
- |
Natural Gas | $114,481 | 26,114 |
MMBtu
|
$4.38 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $55,697 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $41,281 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Water Disposal Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.4133: Use most efficient type of electric motors | $994 | $1,630 |
$511
17,292
kWh
|
$483
-
kW-mo/yr
|
- | - | - | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $10,473 | $18,075 |
$7,132
128,077
kWh
|
$3,341
-
kW-mo/yr
|
- | - | - | |
03 | 2.3212: Optimize plant power factor | $5,202 | $5,124 | - | - | $5,202 | - | - | |
04 | 2.4314: Use synthetic lubricant | $659 | $220 |
$372
12,603
kWh
|
$287
-
kW-mo/yr
|
- | - | - | |
05 | 2.7231: Use radiant heater for spot heating | $13,757 | $55,000 | - | - | - |
$13,757
-
MMBtu
|
- | |
06 | 3.4114: Replace city water with recycled water via cooling tower | $24,612 | $3,100 | - | - | - | - |
$24,612
-
Tgal
|
|
TOTAL RECOMMENDED | $55,697 | $83,149 |
$8,015
157,972
kWh
|
$4,111
-
kW-mo/yr
|
$5,202 |
$13,757
-
MMBtu
|
$24,612
-
Tgal
|
||
TOTAL IMPLEMENTED | $41,281 | $27,929 |
$7,643
145,369
kWh
|
$3,824
-
kW-mo/yr
|
$5,202 | - |
$24,612
-
Tgal
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Water Disposal Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs