Assessment Year | 1995 |
---|---|
Principal Product | Corrugated Containers |
NAICS |
n/a
|
SIC | 2653: Corrugated and Solid Fiber Boxes |
Sales Range | $10 M to 50M |
# of Employees | 120 |
Plant Area |
175,000
ft2
|
Annual Production | 71,000
thousand feet
|
Production Hrs. Annual | 4,160
hrs
|
Location (State) | Kentucky |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $318,107 | 5,022,274 |
kWh
|
$0.063 |
Natural Gas | $73,402 | 44,429 |
MMBtu
|
$1.65 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $48,887 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,046 | $6,889 |
$4,046
63,892
kWh
|
- | |
02 | 2.4133: Use most efficient type of electric motors | $408 | $725 |
$408
6,448
kWh
|
- | |
03 | 2.3212: Optimize plant power factor | $28,107 | $27,720 |
$28,107
-
kWh
|
- | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $8,945 | $50 |
$8,945
141,559
kWh
|
- | |
05 | 2.3212: Optimize plant power factor | $4,224 | $3,600 |
$4,224
-
kWh
|
- | |
06 | 2.4221: Install compressor air intakes in coolest locations | $1,170 | $60 |
$1,170
18,464
kWh
|
- | |
07 | 2.1233: Analyze flue gas for proper air/fuel ratio | $1,987 | $2,000 | - |
$1,987
-
MMBtu
|
|
TOTAL RECOMMENDED | $48,887 | $41,044 |
$46,900
230,363
kWh
|
$1,987
-
MMBtu
|
||
TOTAL IMPLEMENTED | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs