| Assessment Year | 2021 |
|---|---|
| Principal Product | Distilled spirits |
| NAICS | 312140: Distilleries |
| SIC | 2085: Distilled and Blended Liquors |
| Sales Range | $100 M to 500M |
| # of Employees | 100 |
| Plant Area |
1,600,000
ft2
|
| Annual Production | 20,000
Tgal
|
| Production Hrs. Annual | 7,440
hrs
|
| Location (State) | Kentucky |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $489,668 | 20,218,000 |
kWh
|
$0.024 | |
| Electricity Demand | $797,342 | 48,730 |
kW-mo/yr
|
$16.36 | |
| Electricity Fees | $5,200 | - |
|
- | |
| Natural Gas | $1,203,461 | 450,932 |
MMBtu
|
$2.67 | |
| Coal | $1,035,180 | 231,868 |
MMBtu
|
$4.46 | |
| Waste Disposal Costs | |||||
| Water Usage | $297,381 | 61,965 |
Tgal
|
$4.80 | |
| Solid Waste (non-haz) | $57,750 | 4,140,500 |
lb
|
$0.014 | |
| TOTAL YEARLY COSTS | $3,885,982 | ||||
| RECOMMENDED SAVINGS* | $810,579 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | - | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Coal Savings | Other Energy Savings |
|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.6212: Turn off equipment during breaks, reduce operating time | $4,854 | $1,665 |
$4,854
156,570
kWh
|
- | - | - | - | |
| 02 | 2.4239: Eliminate or reduce compressed air usage | $3,964 | - |
$1,968
71,420
kWh
|
$1,996
-
kW-mo/yr
|
- | - | - | |
| 03 | 2.4221: Install compressor air intakes in coolest locations | $685 | $1,660 |
$332
13,838
kWh
|
$353
-
kW-mo/yr
|
- | - | - | |
| 04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $7,035 | $2,510 |
$3,378
140,739
kWh
|
$3,657
-
kW-mo/yr
|
- | - | - | |
| 05 | 2.7221: Lower temperature during the winter season and vice-versa | $330 | $80 |
$330
13,759
kWh
|
- | - | - | - | |
| 06 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $267 | $100 |
$135
4,463
kWh
|
$132
-
kW-mo/yr
|
- | - | - | |
| 07 | 2.7135: Install occupancy sensors | $1,142 | $640 |
$930
38,763
kWh
|
$212
-
kW-mo/yr
|
- | - | - | |
| 08 | 2.3413: Burn fossil fuel to produce steam to drive a steam turbine-generator and use steam exhaust for heat | $731,255 | $3,500,000 |
$143,915
10,279,625
kWh
|
$266,007
-
kW-mo/yr
|
$(-771,542.0)
-
MMBtu
|
$1,092,875
-
MMBtu
|
- | |
| 09 | 2.2442: Preheat combustion air with waste heat | $49,643 | $75,000 | - | - |
$49,643
-
MMBtu
|
- | - | |
| 10 | 2.2511: Insulate bare equipment | $1,250 | $881 | - | - |
$1,250
-
MMBtu
|
- | - | |
| 11 | 2.1321: Replace fossil fuel equipment with electrical equipment | $10,154 | $600 |
$(-379.0)
(-15,188)
kWh
|
- | - | - |
$10,533
-
MMBtu
|
|
| TOTAL RECOMMENDED | $810,579 | $3,583,136 |
$155,463
10,703,989
kWh
|
$272,357
-
kW-mo/yr
|
$(-720,649.0)
-
MMBtu
|
$1,092,875
-
MMBtu
|
$10,533
-
MMBtu
|
||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Coal Savings | Other Energy Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs