Assessment Year | 2018 |
---|---|
Principal Product | Industrial Steel Wire |
NAICS | 331222: Steel Wire Drawing |
SIC | 3315: Steel Wiredrawing and Steel Nails and Spikes |
Sales Range | $50 M to 100M |
# of Employees | 96 |
Plant Area |
275,000
ft2
|
Annual Production | 39,000
ton
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Kentucky |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $1,048,533 | 19,604,849 |
kWh
|
$0.053 | |
Electricity Demand | $241,581 | 33,981 |
kW-mo/yr
|
$7.11 | |
Electricity Fees | $8,280 | - |
|
- | |
Natural Gas | $525,688 | 143,859 |
MMBtu
|
$3.65 | |
Waste Disposal Costs | |||||
Water Usage | $114,708 | 25,679 |
Tgal
|
$4.47 | |
TOTAL YEARLY COSTS | $1,938,790 | ||||
RECOMMENDED SAVINGS* | $115,167 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $44,104 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Usage Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $27,208 | $48,400 |
$23,760
448,280
kWh
|
$3,448
-
kW-mo/yr
|
- | - | |
02 | 2.7135: Install occupancy sensors | $2,773 | $1,959 |
$2,773
52,326
kWh
|
- | - | - | |
03 | 3.4116: Meter recycled water (to reduce sewer charges) | $26,076 | $3,990 | - | - | - |
$26,076
-
Tgal
|
|
04 | 2.4238: Do not use compressed air for personal cooling | $23,118 | $11,500 |
$19,065
359,713
kWh
|
$4,053
-
kW-mo/yr
|
- | - | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $13,263 | $2,190 |
$11,215
211,600
kWh
|
$2,048
-
kW-mo/yr
|
- | - | |
06 | 2.4221: Install compressor air intakes in coolest locations | $860 | $1,250 |
$860
16,235
kWh
|
- | - | - | |
07 | 2.2511: Insulate bare equipment | $8,475 | $2,977 | - | - |
$8,475
-
MMBtu
|
- | |
08 | 2.2511: Insulate bare equipment | $3,719 | $1,526 | - | - |
$3,719
-
MMBtu
|
- | |
09 | 2.2442: Preheat combustion air with waste heat | $3,865 | $5,895 | - | - |
$3,865
-
MMBtu
|
- | |
10 | 2.2442: Preheat combustion air with waste heat | $3,756 | $5,475 | - | - |
$3,756
-
MMBtu
|
- | |
11 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $2,054 | - |
$1,699
32,062
kWh
|
$355
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $115,167 | $85,162 |
$59,372
1,120,216
kWh
|
$9,904
-
kW-mo/yr
|
$19,815
-
MMBtu
|
$26,076
-
Tgal
|
||
TOTAL IMPLEMENTED | $44,104 | $53,799 |
$38,608
728,441
kWh
|
$5,496
-
kW-mo/yr
|
- | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Usage Savings |