| Assessment Year | 2017 |
|---|---|
| Principal Product | Repaired Motors |
| NAICS | 811310: Commercial and Industrial Machinery and Equipment (except Automotive and Electronic) Repair and Main |
| SIC | 7699: Repair Shops and Related Services, Not Elsewhere Classified |
| Sales Range | $10 M to 50M |
| # of Employees | 48 |
| Plant Area |
49,500
ft2
|
| Annual Production | 50,000
units
|
| Production Hrs. Annual | 8,472
hrs
|
| Location (State) | Kentucky |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $51,701 | 831,600 |
kWh
|
$0.062 |
| Electricity Demand | $30,584 | 2,324 |
kW-mo/yr
|
$13.16 |
| Electricity Fees | $34,014 | - |
|
- |
| Natural Gas | $32,386 | 5,185 |
MMBtu
|
$6.25 |
| TOTAL YEARLY COSTS | $148,685 | |||
| RECOMMENDED SAVINGS* | $33,479 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $16,803 | $12,299 |
$12,921
208,411
kWh
|
$3,882
-
kW-mo/yr
|
- | |
| 02 | 2.7111: Reduce illumination to minimum necessary levels | $1,073 | $263 |
$1,073
17,301
kWh
|
- | - | |
| 03 | 2.7124: Make a practice of turning off lights when not needed | $543 | - |
$543
8,754
kWh
|
- | - | |
| 04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,482 | $2,189 |
$2,679
43,207
kWh
|
$803
-
kW-mo/yr
|
- | |
| 05 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,142 | - |
$879
14,183
kWh
|
$263
-
kW-mo/yr
|
- | |
| 06 | 2.4221: Install compressor air intakes in coolest locations | $394 | $683 |
$394
6,361
kWh
|
- | - | |
| 07 | 2.1233: Analyze flue gas for proper air/fuel ratio | $4,530 | $1,500 | - | - |
$4,530
-
MMBtu
|
|
| 08 | 3.1161: Eliminate/reduce an operation | $3,032 | - |
$2,006
32,349
kWh
|
$1,026
-
kW-mo/yr
|
- | |
| 09 | 2.6212: Turn off equipment during breaks, reduce operating time | $309 | - |
$309
4,987
kWh
|
- | - | |
| 10 | 2.7224: Reduce space conditioning during non-working hours | $1,207 | - |
$402
6,480
kWh
|
- |
$805
-
MMBtu
|
|
| 11 | 2.7224: Reduce space conditioning during non-working hours | $964 | - |
$964
15,552
kWh
|
- | - | |
| TOTAL RECOMMENDED | $33,479 | $16,934 |
$22,170
357,585
kWh
|
$5,974
-
kW-mo/yr
|
$5,335
-
MMBtu
|
||
| TOTAL IMPLEMENTED | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs