Assessment Year | 2017 |
---|---|
Principal Product | Men's and Women's Clothing |
NAICS | 315220: Men’s and Boys’ Cut and Sew Apparel Manufacturing |
SIC | 2326: Men's and Boys' Work Clothing |
Sales Range | $100 M to 500M |
# of Employees | 710 |
Plant Area |
840,000
ft2
|
Annual Production | 2,600,000
units
|
Production Hrs. Annual | 6,600
hrs
|
Location (State) | Kentucky |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $382,064 | 11,024,000 |
kWh
|
$0.035 | |
Electricity Demand | $420,425 | 20,213 |
kW-mo/yr
|
$20.80 | |
Electricity Fees | $5,361 | - |
|
- | |
Natural Gas | $20,201 | 5,977 |
MMBtu
|
$3.38 | |
Waste Disposal Costs | |||||
Water Usage | $7,519 | 1,153 |
Tgal
|
$6.52 | |
Water Disposal | $19,916 | 1,153 |
Tgal
|
$17.27 | |
TOTAL YEARLY COSTS | $855,486 | ||||
RECOMMENDED SAVINGS* | $186,484 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Usage Savings | Water Disposal Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $66,864 | $7,493 |
$32,170
919,144
kWh
|
$34,694
-
kW-mo/yr
|
- | - | - | - | |
02 | 2.7124: Make a practice of turning off lights when not needed | $37,683 | - |
$18,110
517,440
kWh
|
$19,573
-
kW-mo/yr
|
- | - | - | - | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $11,140 | $11,343 |
$3,527
100,769
kWh
|
$7,613
-
kW-mo/yr
|
- | - | - | - | |
04 | 2.7135: Install occupancy sensors | $1,664 | $1,288 |
$1,664
47,544
kWh
|
- | - | - | - | - | |
05 | 2.4152: Use only certified motor repair shops | $15,253 | - |
$2,358
67,381
kWh
|
$2,538
-
kW-mo/yr
|
- | - | - | $10,357 | |
06 | 2.6212: Turn off equipment during breaks, reduce operating time | $2,154 | $926 |
$2,154
61,545
kWh
|
- | - | - | - | - | |
07 | 2.7224: Reduce space conditioning during non-working hours | $25,486 | - |
$25,486
728,160
kWh
|
- | - | - | - | - | |
08 | 2.7224: Reduce space conditioning during non-working hours | $10,498 | - |
$8,909
254,544
kWh
|
- |
$1,589
-
MMBtu
|
- | - | - | |
09 | 3.4155: Meter waste water | $6,463 | - | - | - | - |
$1,765
-
Tgal
|
$4,698
-
Tgal
|
- | |
10 | 3.4155: Meter waste water | $2,076 | $253 | - | - | - | - |
$2,076
-
Tgal
|
- | |
11 | 2.4231: Reduce the pressure of compressed air to the minimum required | $2,508 | - |
$2,508
71,652
kWh
|
- | - | - | - | - | |
12 | 2.4322: Use or replace with energy efficient substitutes | $905 | $1,053 |
$260
7,426
kWh
|
$645
-
kW-mo/yr
|
- | - | - | - | |
13 | 2.4239: Eliminate or reduce compressed air usage | $3,790 | $3,458 |
$3,790
108,291
kWh
|
- | - | - | - | - | |
TOTAL RECOMMENDED | $186,484 | $25,814 |
$100,936
2,883,896
kWh
|
$65,063
-
kW-mo/yr
|
$1,589
-
MMBtu
|
$1,765
-
Tgal
|
$6,774
-
Tgal
|
$10,357 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Usage Savings | Water Disposal Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs