Assessment Year | 2017 |
---|---|
Principal Product | Wastewater |
NAICS | 221320: Sewage Treatment Facilities |
SIC | 4952: Sewerage Systems |
Sales Range | less than $500 k |
# of Employees | 5 |
Plant Area |
65,000
ft2
|
Annual Production | 596,000
Tgal
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Kentucky |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $109,139 | 1,851,480 |
kWh
|
$0.059 |
Electricity Demand | $35,629 | 3,733 |
kW-mo/yr
|
$9.54 |
Electricity Fees | $4,217 | - |
|
- |
TOTAL YEARLY COSTS | $148,985 | |||
RECOMMENDED SAVINGS* | $94,170 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $217 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Ancillary Material Cost Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $46,813 | $31,719 |
$41,089
696,420
kWh
|
$5,724
-
kW-mo/yr
|
- | - | |
02 | 2.4322: Use or replace with energy efficient substitutes | $5,465 | $26,520 |
$3,198
54,203
kWh
|
$2,267
-
kW-mo/yr
|
- | - | |
03 | 2.4321: Upgrade obsolete equipment | $2,904 | - |
$2,904
49,220
kWh
|
- | - | - | |
04 | 2.7111: Reduce illumination to minimum necessary levels | $14,895 | - |
$6,822
115,632
kWh
|
$754
-
kW-mo/yr
|
$7,319 | - | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $986 | $1,253 |
$862
14,606
kWh
|
$124
-
kW-mo/yr
|
- | - | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $461 | $762 |
$289
4,894
kWh
|
$172
-
kW-mo/yr
|
- | - | |
07 | 2.7124: Make a practice of turning off lights when not needed | $217 | - |
$217
3,686
kWh
|
- | - | - | |
08 | 2.4156: Establish a preventative maintenance program | $333 | - | - | - | - | $333 | |
09 | 2.3415: Use a fossil fuel engine to cogenerate electricity or motive power; and utilize heat | $22,096 | $78,750 |
$18,089
306,600
kWh
|
$4,007
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $94,170 | $139,004 |
$73,470
1,245,261
kWh
|
$13,048
-
kW-mo/yr
|
$7,319 | $333 | ||
TOTAL IMPLEMENTED | $217 | - |
$217
3,686
kWh
|
- | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Ancillary Material Cost Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs