Assessment Year | 2013 |
---|---|
Principal Product | Linear actuation systems |
NAICS | 333995: Fluid Power Cylinder and Actuator Manufacturing |
SIC | 3593: Fluid Power Cylinders and Actuators |
Sales Range | $100 M to 500M |
# of Employees | 200 |
Plant Area |
125,000
ft2
|
Annual Production | 725,000
pieces
|
Production Hrs. Annual | 4,000
hrs
|
Location (State) | Kentucky |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $71,200 | 1,738,400 |
kWh
|
$0.041 |
Electricity Demand | $64,785 | 4,502 |
kW-mo/yr
|
$14.39 |
Electricity Fees | $10,441 | - |
|
- |
Natural Gas | $19,970 | 3,294 |
MMBtu
|
$6.06 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $39,276 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $39,276 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.7243: Improve air circulation with destratification fans / other methods | $12,434 | $44,000 |
$2,510
61,300
kWh
|
$3,100
-
kW-mo/yr
|
- |
$6,824
-
MMBtu
|
|
02 | 2.7232: Replace existing hvac unit with high efficiency model | $7,512 | $28,560 |
$2,751
67,100
kWh
|
$4,634
-
kW-mo/yr
|
- |
$127
-
MMBtu
|
|
03 | 2.2437: Recover waste heat from equipment | $3,739 | $4,500 | - | - | - |
$3,739
-
MMBtu
|
|
04 | 2.6212: Turn off equipment during breaks, reduce operating time | $5,453 | $15,000 |
$5,453
133,000
kWh
|
- | - | - | |
05 | 2.7111: Reduce illumination to minimum necessary levels | $4,066 | - |
$2,374
59,000
kWh
|
$1,692
-
kW-mo/yr
|
- | - | |
06 | 2.8114: Change rate schedules or other changes in utility service | $2,594 | - | - | - | $2,594 | - | |
07 | 2.6218: Turn off equipment when not in use | $1,662 | $650 |
$1,107
27,011
kWh
|
$555
-
kW-mo/yr
|
- | - | |
08 | 2.4221: Install compressor air intakes in coolest locations | $798 | $700 |
$539
13,140
kWh
|
$259
-
kW-mo/yr
|
- | - | |
09 | 2.7134: Use photocell controls | $328 | $592 |
$328
8,000
kWh
|
- | - | - | |
10 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $690 | $690 |
$466
11,357
kWh
|
$224
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $39,276 | $94,692 |
$15,528
379,908
kWh
|
$10,464
-
kW-mo/yr
|
$2,594 |
$10,690
-
MMBtu
|
||
TOTAL IMPLEMENTED | $39,276 | $94,692 |
$15,528
379,908
kWh
|
$10,464
-
kW-mo/yr
|
$2,594 |
$10,690
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs