Assessment Year | 2012 |
---|---|
Principal Product | Retail Chicken |
NAICS | 311615: Poultry Processing |
SIC | 2015: Poultry Slaughtering and Processing |
Sales Range | greater than $500 M |
# of Employees | 1,255 |
Plant Area |
193,000
ft2
|
Annual Production | 293,402,000
lb
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Kentucky |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,149,276 | 29,650,458 |
kWh
|
$0.039 |
Electricity Demand | $773,515 | 59,639 |
kW-mo/yr
|
$12.97 |
Electricity Fees | $(-237,288.0) | - |
|
- |
Natural Gas | $307,268 | 90,800 |
MMBtu
|
$3.38 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $97,259 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $11,568 | $12,500 |
$9,400
242,277
kWh
|
$2,168
-
kW-mo/yr
|
- | |
02 | 2.7111: Reduce illumination to minimum necessary levels | $7,955 | $5,000 |
$4,842
124,800
kWh
|
$3,113
-
kW-mo/yr
|
- | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $5,598 | $2,240 |
$3,158
81,405
kWh
|
$2,440
-
kW-mo/yr
|
- | |
04 | 2.6231: Utilize controls to operate equipment only when needed | $4,202 | $500 |
$4,202
108,290
kWh
|
- | - | |
05 | 2.7111: Reduce illumination to minimum necessary levels | $1,591 | $1,000 |
$968
24,960
kWh
|
$623
-
kW-mo/yr
|
- | |
06 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $521 | $180 |
$273
7,034
kWh
|
$248
-
kW-mo/yr
|
- | |
07 | 2.2437: Recover waste heat from equipment | $52,633 | $52,000 | - | - |
$52,633
-
MMBtu
|
|
08 | 2.1232: Keep boiler tubes clean | $6,493 | $2,410 | - | - |
$6,493
-
MMBtu
|
|
09 | 2.1233: Analyze flue gas for proper air/fuel ratio | $4,708 | $100 | - | - |
$4,708
-
MMBtu
|
|
10 | 2.2136: Install / repair insulation on steam lines | $1,990 | $1,060 | - | - |
$1,990
-
MMBtu
|
|
TOTAL RECOMMENDED | $97,259 | $76,990 |
$22,843
588,766
kWh
|
$8,592
-
kW-mo/yr
|
$65,824
-
MMBtu
|
||
TOTAL IMPLEMENTED | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |