| Assessment Year | 2011 |
|---|---|
| Principal Product | Printed Circuit Boards |
| NAICS | 334412: Bare Printed Circuit Board Manufacturing |
| SIC | 3672: Printed Circuit Boards |
| Sales Range | $10 M to 50M |
| # of Employees | 85 |
| Plant Area |
36,291
ft2
|
| Annual Production | 150,000
units
|
| Production Hrs. Annual | 4,080
hrs
|
| Location (State) | Florida |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $284,630 | 2,530,737 |
kWh
|
$0.11 |
| Electricity Demand | $41,890 | 7,637 |
kW-mo/yr
|
$5.49 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $61,243 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
|---|---|---|---|---|---|---|
| 01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $14,683 | - |
$14,683
121,509
kWh
|
- | |
| 02 | 2.4225: Install common header on compressors | $1,378 | $511 |
$1,378
12,307
kWh
|
- | |
| 03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,667 | $470 |
$3,667
28,427
kWh
|
- | |
| 04 | 2.4226: Use / purchase optimum sized compressor | $5,110 | - |
$4,819
43,027
kWh
|
$291
-
kW-mo/yr
|
|
| 05 | 2.6218: Turn off equipment when not in use | $24,031 | - |
$24,031
211,491
kWh
|
- | |
| 06 | 2.4227: Use compressor air filters | $2,246 | $270 |
$2,103
18,779
kWh
|
$143
-
kW-mo/yr
|
|
| 07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,013 | $5,903 |
$4,409
39,362
kWh
|
$604
-
kW-mo/yr
|
|
| 08 | 2.6218: Turn off equipment when not in use | $2,431 | - |
$2,431
18,842
kWh
|
- | |
| 09 | 2.7425: Clean or color roof to reduce solar load | $1,074 | $3,066 |
$1,074
9,592
kWh
|
- | |
| 10 | 2.7229: Air condition only space necessary | $204 | $17 |
$204
1,581
kWh
|
- | |
| 11 | 2.7211: Clean and maintain refrigerant condensers and towers | $1,406 | $109 |
$1,269
11,326
kWh
|
$137
-
kW-mo/yr
|
|
| TOTAL RECOMMENDED | $61,243 | $10,346 |
$60,068
516,243
kWh
|
$1,175
-
kW-mo/yr
|
||
| TOTAL IMPLEMENTED | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs