Assessment Year | 2011 |
---|---|
Principal Product | medical devices |
NAICS | 325412: Pharmaceutical Preparation Manufacturing |
SIC | 2834: Pharmaceutical Preparations |
Sales Range | $50 M to 100M |
# of Employees | 120 |
Plant Area |
40,000
ft2
|
Annual Production | 25,000,000
pieces
|
Production Hrs. Annual | 2,184
hrs
|
Location (State) | Florida |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $81,309 | 851,110 |
kWh
|
$0.096 |
Electricity Demand | $28,906 | 2,664 |
kW-mo/yr
|
$10.85 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $18,758 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $4,813 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $493 | - |
$276
2,877
kWh
|
$217
-
kW-mo/yr
|
|
02 | 2.4225: Install common header on compressors | $138 | $280 |
$138
1,439
kWh
|
- | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $853 | $482 |
$853
6,611
kWh
|
- | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,832 | $5,165 |
$3,598
37,477
kWh
|
$2,234
-
kW-mo/yr
|
|
05 | 2.7135: Install occupancy sensors | $1,884 | $1,676 |
$1,884
14,603
kWh
|
- | |
06 | 2.7124: Make a practice of turning off lights when not needed | $697 | - |
$697
7,258
kWh
|
- | |
07 | 2.7496: Install partitions to reduce size of conditioned space | $3,726 | $1,919 |
$3,726
28,882
kWh
|
- | |
08 | 2.7425: Clean or color roof to reduce solar load | $2,799 | $7,128 |
$2,799
21,695
kWh
|
- | |
09 | 2.6211: Conserve energy by efficient use of vending machines | $659 | $686 |
$659
6,800
kWh
|
- | |
10 | 2.7229: Air condition only space necessary | $227 | $21 |
$227
1,757
kWh
|
- | |
11 | 2.2515: Use optimum thickness insulation | $1,450 | $576 |
$1,450
11,244
kWh
|
- | |
TOTAL RECOMMENDED | $18,758 | $17,933 |
$16,307
140,643
kWh
|
$2,451
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | $4,813 | $2,865 |
$4,596
39,906
kWh
|
$217
-
kW-mo/yr
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs