| Assessment Year | 2011 |
|---|---|
| Principal Product | soda, soft drinks |
| NAICS | 312111: Soft Drink Manufacturing |
| SIC | 2086: Bottled and Canned Soft Drinks and Carbonated Waters |
| Sales Range | $10 M to 50M |
| # of Employees | 90 |
| Plant Area |
192,000
ft2
|
| Annual Production | 11,000,000
units
|
| Production Hrs. Annual | 5,460
hrs
|
| Location (State) | Florida |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $526,621 | 7,574,423 |
kWh
|
$0.070 |
| Electricity Demand | $192,763 | 17,071 |
kW-mo/yr
|
$11.29 |
| Natural Gas | $103,559 | 16,623 |
MMBtu
|
$6.23 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $107,724 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.7226: Use computer programs to optimize hvac performance | $43,145 | $25,340 |
$41,903
625,275
kWh
|
$1,242
-
kW-mo/yr
|
- | |
| 02 | 2.7425: Clean or color roof to reduce solar load | $3,404 | $5,896 |
$3,325
35,838
kWh
|
$79
-
kW-mo/yr
|
- | |
| 03 | 2.6211: Conserve energy by efficient use of vending machines | $1,173 | $1,818 |
$1,173
17,000
kWh
|
- | - | |
| 04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $8,370 | $3,778 |
$8,370
88,102
kWh
|
- | - | |
| 05 | 2.6231: Utilize controls to operate equipment only when needed | $28,580 | $12,180 |
$28,580
300,846
kWh
|
- | - | |
| 06 | 2.1131: Repair faulty insulation in furnaces, boilers, etc | $136 | $244 | - | - |
$136
-
MMBtu
|
|
| 07 | 2.1222: Install turbulators | $3,745 | $3,750 | - | - |
$3,745
-
MMBtu
|
|
| 08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $14,493 | $9,387 |
$14,087
139,040
kWh
|
$406
-
kW-mo/yr
|
- | |
| 09 | 2.7135: Install occupancy sensors | $2,620 | $243 |
$2,620
37,973
kWh
|
- | - | |
| 10 | 2.7442: Keep doors and windows shut when not on use | $635 | - |
$635
9,205
kWh
|
- | - | |
| 11 | 2.7228: Avoid introducing hot, humid, or dirty air into hvac system | $1,423 | $840 |
$1,389
14,978
kWh
|
$34
-
kW-mo/yr
|
- | |
| TOTAL RECOMMENDED | $107,724 | $63,476 |
$102,082
1,268,257
kWh
|
$1,761
-
kW-mo/yr
|
$3,881
-
MMBtu
|
||
| TOTAL IMPLEMENTED | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs