Assessment Year | 2010 |
---|---|
Principal Product | Artificial Knee / Prosthetics |
NAICS | 339113: Surgical Appliance and Supplies Manufacturing |
SIC | 3842: Orthopedic, Prosthetic, and Surgical Appliances and Supplies |
Sales Range | $100 M to 500M |
# of Employees | 370 |
Plant Area |
54,755
ft2
|
Annual Production | 168,000
pieces
|
Production Hrs. Annual | 4,290
hrs
|
Location (State) | Florida |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $449,967 | 4,693,120 |
kWh
|
$0.096 |
Electricity Demand | $99,895 | 10,824 |
kW-mo/yr
|
$9.23 |
Electricity Fees | $64,103 | - |
|
- |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $78,933 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Solid Waste (non-haz) Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4235: Remove or close off unneeded compressed air lines | $3,268 | $1,893 |
$3,268
30,258
kWh
|
- | - | - | |
02 | 2.4221: Install compressor air intakes in coolest locations | $3,786 | $4,195 |
$3,786
35,052
kWh
|
- | - | - | |
03 | 2.4227: Use compressor air filters | $1,326 | $210 |
$1,326
10,120
kWh
|
- | - | - | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,057 | $401 |
$1,057
8,069
kWh
|
- | - | - | |
05 | 2.4239: Eliminate or reduce compressed air usage | $18,101 | $4,865 |
$18,101
138,179
kWh
|
- | - | - | |
06 | 2.4231: Reduce the pressure of compressed air to the minimum required | $8,388 | - |
$8,388
64,032
kWh
|
- | - | - | |
07 | 2.7135: Install occupancy sensors | $1,414 | $1,926 |
$1,414
13,092
kWh
|
- | - | - | |
08 | 2.7111: Reduce illumination to minimum necessary levels | $1,980 | $881 |
$1,620
14,716
kWh
|
$360
-
kW-mo/yr
|
- | - | |
09 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $14,310 | $20,000 |
$14,310
109,240
kWh
|
- | - | - | |
10 | 2.7111: Reduce illumination to minimum necessary levels | $1,649 | $232 |
$1,289
12,271
kWh
|
$360
-
kW-mo/yr
|
- | - | |
11 | 2.7121: Utilize daylight whenever possible in lieu of artificial light | $4,515 | $7,701 |
$4,515
41,808
kWh
|
- | - | - | |
12 | 2.7243: Improve air circulation with destratification fans / other methods | $5,125 | $2,284 |
$5,125
39,127
kWh
|
- | - | - | |
13 | 2.7225: Close outdoor air dampers during warm-up / cool-down periods | $1,875 | $10,480 |
$1,875
14,314
kWh
|
- | - | - | |
14 | 2.8121: Apply for tax-free status for energy purchases | $11,568 | - | - | - | - | $11,568 | |
15 | 3.5318: Recycle fluorescent lamps | $571 | $3,405 | - | - |
$571
-
lb
|
- | |
TOTAL RECOMMENDED | $78,933 | $58,473 |
$66,074
530,278
kWh
|
$720
-
kW-mo/yr
|
$571
-
lb
|
$11,568 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Solid Waste (non-haz) Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs