Assessment Year | 2007 |
---|---|
Principal Product | Milk |
NAICS | 311511: Fluid Milk Manufacturing |
SIC | 2026: Fluid Milk |
Sales Range | $50 M to 100M |
# of Employees | 150 |
Plant Area |
140,000
ft2
|
Annual Production | 40,000
Tgal
|
Production Hrs. Annual | 7,956
hrs
|
Location (State) | Florida |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $938,245 | 12,867,277 |
kWh
|
$0.073 |
Electricity Demand | $196,400 | 46,447 |
kW-mo/yr
|
$4.23 |
Natural Gas | $357,502 | 44,759 |
MMBtu
|
$7.99 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $306,997 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $48,081 | $134,669 |
$44,401
608,227
kWh
|
$3,680
-
kW-mo/yr
|
- | |
02 | 2.7111: Reduce illumination to minimum necessary levels | $940 | - |
$793
10,857
kWh
|
$147
-
kW-mo/yr
|
- | |
03 | 2.7141: Lower light fixtures in high ceiling areas | $477 | $150 |
$436
5,975
kWh
|
$41
-
kW-mo/yr
|
- | |
04 | 2.7135: Install occupancy sensors | $806 | $118 |
$806
11,046
kWh
|
- | - | |
05 | 2.2113: Repair or replace steam traps | $4,676 | $218 | - | - |
$4,676
-
MMBtu
|
|
06 | 2.7447: Install vinyl strip / high speed / air curtain doors | $3,060 | $1,600 |
$3,060
41,913
kWh
|
- | - | |
07 | 2.2515: Use optimum thickness insulation | $32,078 | $6,105 |
$32,078
400,979
kWh
|
- | - | |
08 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $547 | - |
$547
5,363
kWh
|
- | - | |
09 | 2.4133: Use most efficient type of electric motors | $6,769 | $19,429 |
$6,185
84,848
kWh
|
$584
-
kW-mo/yr
|
- | |
10 | 2.3212: Optimize plant power factor | $209,563 | $17,000 |
$192,051
2,584,624
kWh
|
$17,512
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $306,997 | $179,289 |
$280,357
3,753,832
kWh
|
$21,964
-
kW-mo/yr
|
$4,676
-
MMBtu
|
||
TOTAL IMPLEMENTED | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs