Assessment Year | 2006 |
---|---|
Principal Product | Nylon |
NAICS | 325220: Artificial and Synthetic Fibers and Filaments Manufacturing |
SIC | 2824: Manmade Organic Fibers, Except Cellulosic |
Sales Range | n/a |
# of Employees | 1,700 |
Plant Area |
1,742,400
ft2
|
Annual Production | 490,000,000
lb
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Florida |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $2,210,174 | 49,686,500 |
kWh
|
$0.044 |
Electricity Demand | $458,877 | 154,848 |
kW-mo/yr
|
$2.96 |
Natural Gas | $229,412 | 22,941 |
MMBtu
|
$10.00 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $437,952 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $433,577 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,443 | $1,104 |
$277
10,162
kWh
|
$41
-
kW-mo/yr
|
$1,125 | |
02 | 2.7124: Make a practice of turning off lights when not needed | $886 | - |
$623
22,834
kWh
|
$263
-
kW-mo/yr
|
- | |
03 | 2.7135: Install occupancy sensors | $961 | $353 |
$804
29,467
kWh
|
$157
-
kW-mo/yr
|
- | |
04 | 2.6231: Utilize controls to operate equipment only when needed | $388,094 | $48,067 |
$327,265
11,987,724
kWh
|
$60,829
-
kW-mo/yr
|
- | |
05 | 2.7131: Add area lighting switches | $1,085 | $4,305 |
$1,085
39,735
kWh
|
- | - | |
06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $44,780 | $2,688 |
$44,780
1,226,829
kWh
|
- | - | |
07 | 3.1181: Eliminate a by-product | $703 | $160 |
$703
19,256
kWh
|
- | - | |
TOTAL RECOMMENDED | $437,952 | $56,677 |
$375,537
13,336,007
kWh
|
$61,290
-
kW-mo/yr
|
$1,125 | ||
TOTAL IMPLEMENTED | $433,577 | $50,915 |
$372,748
13,233,809
kWh
|
$60,829
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs