Assessment Year | 2002 |
---|---|
Principal Product | Fruit Juice |
NAICS |
n/a
|
SIC | 2033: Canned Fruits, Vegetables, Preserves, Jams, and Jellies |
Sales Range | $100 M to 500M |
# of Employees | 150 |
Plant Area |
645,712
ft2
|
Annual Production | 14,000
pieces
|
Production Hrs. Annual | 7,488
hrs
|
Location (State) | Florida |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,060,575 | 25,045,155 |
kWh
|
$0.042 |
Electricity Demand | $87,679 | 52,770 |
kW-mo/yr
|
$1.66 |
Other Energy | $163,737 | 20,919 |
MMBtu
|
$7.83 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $282,308 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $261,605 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Solid Waste (non-haz) Savings | Administrative Changes Savings | Ancillary Material Cost Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.7124: Make a practice of turning off lights when not needed | $1,600 | - |
$1,600
34,047
kWh
|
- | - | - | - | - | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,781 | $7,711 |
$3,502
81,434
kWh
|
$279
-
kW-mo/yr
|
- | - | - | - | |
03 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $4,292 | - |
$2,796
59,492
kWh
|
- | - | $177 | $1,319 | - | |
04 | 2.4133: Use most efficient type of electric motors | $4,330 | $11,809 |
$3,954
91,942
kWh
|
$376
-
kW-mo/yr
|
- | - | - | - | |
05 | 2.4221: Install compressor air intakes in coolest locations | $1,512 | $2,000 |
$1,512
32,171
kWh
|
- | - | - | - | - | |
06 | 2.7111: Reduce illumination to minimum necessary levels | $1,120 | $80 |
$1,052
24,461
kWh
|
$68
-
kW-mo/yr
|
- | - | - | - | |
07 | 2.4231: Reduce the pressure of compressed air to the minimum required | $29,843 | - |
$29,843
634,959
kWh
|
- | - | - | - | - | |
08 | 2.7491: Insulate glazing, walls, ceilings, and roofs | $44,131 | $172,405 |
$44,131
938,961
kWh
|
- | - | - | - | - | |
09 | 3.5212: Regrind, reuse, or sell scrap plastic parts | $10,961 | - | - | - |
$10,961
-
lb
|
- | - | - | |
10 | 2.8114: Change rate schedules or other changes in utility service | $180,738 | - | - | - | - | - | - | $180,738 | |
TOTAL RECOMMENDED | $282,308 | $194,005 |
$88,390
1,897,467
kWh
|
$723
-
kW-mo/yr
|
$10,961
-
lb
|
$177 | $1,319 | $180,738 | ||
TOTAL IMPLEMENTED | $261,605 | $182,116 |
$80,588
1,721,572
kWh
|
$279
-
kW-mo/yr
|
- | - | - | $180,738 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Solid Waste (non-haz) Savings | Administrative Changes Savings | Ancillary Material Cost Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs