Assessment Year | 1998 |
---|---|
Principal Product | Newspaper Printing and Publishing |
NAICS |
n/a
|
SIC | 2711: Newspapers: Publishing, or Publishing and Printing |
Sales Range | $50 M to 100M |
# of Employees | 430 |
Plant Area |
180,000
ft2
|
Annual Production | 3,500,000
pieces
|
Production Hrs. Annual | 6,753
hrs
|
Location (State) | Florida |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $410,902 | 8,985,639 |
kWh
|
$0.046 |
Electricity Demand | $205,598 | 23,040 |
kW-mo/yr
|
$8.92 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $63,028 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $21,106 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $13,048 | $40,581 |
$9,150
199,004
kWh
|
$3,898
-
kW-mo/yr
|
- | |
02 | 2.7135: Install occupancy sensors | $6,122 | $9,656 |
$6,122
133,060
kWh
|
- | - | |
03 | 2.4133: Use most efficient type of electric motors | $551 | $5,948 |
$345
7,620
kWh
|
$206
-
kW-mo/yr
|
- | |
04 | 2.4226: Use / purchase optimum sized compressor | $7,361 | $3,316 |
$4,085
88,804
kWh
|
$3,276
-
kW-mo/yr
|
- | |
05 | 2.2437: Recover waste heat from equipment | $10,820 | $4,000 |
$6,077
132,181
kWh
|
$4,743
-
kW-mo/yr
|
- | |
06 | 3.5248: Separate and recycle scrap metal to foundry or for sale | $3,450 | - | - | - | $3,450 | |
07 | 3.5311: Recover and reuse waste material | $570 | - | - | - | $570 | |
08 | 4.812: Apply for investment incentives | $21,106 | - | - | - | $21,106 | |
TOTAL RECOMMENDED | $63,028 | $63,501 |
$25,779
560,669
kWh
|
$12,123
-
kW-mo/yr
|
$25,126 | ||
TOTAL IMPLEMENTED | $21,106 | - | - | - | $21,106 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs