Assessment Year | 1997 |
---|---|
Principal Product | Vegetable Concentrates |
NAICS |
n/a
|
SIC | 2087: Flavoring Extracts and Flavoring Syrups, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 45 |
Plant Area |
45,000
ft2
|
Annual Production | 20,000
ton
|
Production Hrs. Annual | 4,784
hrs
|
Location (State) | Florida |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $74,113 | 1,277,550 |
kWh
|
$0.058 |
Electricity Demand | $17,015 | 4,616 |
kW-mo/yr
|
$3.69 |
Natural Gas | $138,779 | 23,733 |
MMBtu
|
$5.85 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $37,782 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $19,809 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Solid Waste (non-haz) Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.2414: Use waste heat from hot flue gases to preheat | $5,816 | $15,515 | - | - |
$5,816
-
MMBtu
|
- | - | |
02 | 2.4133: Use most efficient type of electric motors | $252 | $252 |
$199
3,517
kWh
|
$53
-
kW-mo/yr
|
- | - | - | |
03 | 2.1233: Analyze flue gas for proper air/fuel ratio | $1,782 | $1,000 | - | - |
$1,782
-
MMBtu
|
- | - | |
04 | 2.2136: Install / repair insulation on steam lines | $2,851 | $451 | - | - |
$2,851
-
MMBtu
|
- | - | |
05 | 2.2511: Insulate bare equipment | $1,170 | $974 |
$1,170
20,223
kWh
|
- | - | - | - | |
06 | 2.2123: Insulate feedwater tank | $1,304 | $200 | - | - |
$1,304
-
MMBtu
|
- | - | |
07 | 3.1291: Eliminate practice of mixing waste streams | $1,261 | $5,000 | - | - | - | - | $1,261 | |
08 | 3.6192: Use a less expensive method of waste removal | $3,613 | - | - | - | - |
$3,613
-
lb
|
- | |
09 | 4.213: Purchase material from supplier in customized packaging | $4,655 | $1,800 | - | - | - | - | $4,655 | |
10 | 4.231: Purchase equipment instead of leasing | $12,450 | $15,000 | - | - | - | - | $12,450 | |
11 | 2.8121: Apply for tax-free status for energy purchases | $2,628 | - | - | - | - | - | $2,628 | |
TOTAL RECOMMENDED | $37,782 | $40,192 |
$1,369
23,740
kWh
|
$53
-
kW-mo/yr
|
$11,753
-
MMBtu
|
$3,613
-
lb
|
$20,994 | ||
TOTAL IMPLEMENTED | $19,809 | $17,877 |
$1,369
23,740
kWh
|
$53
-
kW-mo/yr
|
$5,937
-
MMBtu
|
- | $12,450 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Solid Waste (non-haz) Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs