Assessment Year 1993
Principal Product POLYYURETHANE FOAM
NAICS
n/a
SIC 3086: Plastics Foam Products
Sales Range $500
k
to 1
M
# of Employees 120
Plant Area 175,000
ft2
Annual Production 124,000
thousand feet
Production Hrs. Annual 5,460
hrs
Location (State) Florida

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $202,701 3,305,393
kWh
Natural Gas $42,562 7,197
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $62,993 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $16,285

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Natural Gas Savings
01 2.7142: Utilize higher efficiency lamps and/or ballasts $5,736 $17,345 $5,736
94,080
kWh
-
02 2.7111: Reduce illumination to minimum necessary levels $21,182 $1,060 $21,182
347,304
kWh
-
03 2.7142: Utilize higher efficiency lamps and/or ballasts $18,545 $5,513 $18,545
303,927
kWh
-
04 2.7142: Utilize higher efficiency lamps and/or ballasts $431 $391 $431
7,034
kWh
-
05 2.1233: Analyze flue gas for proper air/fuel ratio $1,347 $1,000 - $1,347
-
MMBtu
06 2.4133: Use most efficient type of electric motors $10,938 $20,958 $10,938
179,367
kWh
-
07 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $2,816 $1,000 $2,816
46,307
kWh
-
08 2.4221: Install compressor air intakes in coolest locations $236 $500 $236
3,810
kWh
-
09 2.7232: Replace existing hvac unit with high efficiency model $488 $2,000 $488
7,913
kWh
-
10 2.7492: Use proper thickness of insulation on building envelope $814 $1,392 $814
13,482
kWh
-
11 2.2136: Install / repair insulation on steam lines $460 $407 - $460
-
MMBtu
TOTAL RECOMMENDED $62,993 $51,566 $61,186
1,003,224
kWh
$1,807
-
MMBtu
TOTAL IMPLEMENTED $16,285 $25,865 $14,478
237,397
kWh
$1,807
-
MMBtu
Yearly Savings* Imp'd Cost* Electricity Usage Savings Natural Gas Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs