| Assessment Year | 1993 |
|---|---|
| Principal Product | Newspaper |
| NAICS |
n/a
|
| SIC | 2711: Newspapers: Publishing, or Publishing and Printing |
| Sales Range | $5 M to 10M |
| # of Employees | 320 |
| Plant Area |
62,000
ft2
|
| Annual Production | 27,375,000
pieces
|
| Production Hrs. Annual | 8,736
hrs
|
| Location (State) | Florida |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $263,545 | 3,804,220 |
kWh
|
$0.069 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $114,496 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $42,942 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings |
|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,012 | $2,142 |
$1,012
14,654
kWh
|
|
| 02 | 2.7144: Install spectral reflectors / delamp | $20,185 | $28,015 |
$20,185
242,087
kWh
|
|
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $354 | $1,320 |
$354
1,758
kWh
|
|
| 04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $512 | $130 |
$512
7,327
kWh
|
|
| 05 | 2.7232: Replace existing hvac unit with high efficiency model | $14,911 | $17,020 |
$14,911
216,002
kWh
|
|
| 06 | 2.4133: Use most efficient type of electric motors | $9,228 | $9,376 |
$9,228
133,646
kWh
|
|
| 07 | 2.7491: Insulate glazing, walls, ceilings, and roofs | $28,637 | $77,160 |
$28,637
415,006
kWh
|
|
| 08 | 2.4224: Upgrade controls on compressors | $17,131 | $1,500 |
$17,131
248,242
kWh
|
|
| 09 | 2.7271: Replace electric reheat with heat pipes | $21,866 | $22,500 |
$21,866
122,802
kWh
|
|
| 10 | 2.3137: Use power during off-peak periods | $660 | - |
$660
-
kWh
|
|
| TOTAL RECOMMENDED | $114,496 | $159,163 |
$114,496
1,401,524
kWh
|
||
| TOTAL IMPLEMENTED | $42,942 | $30,038 |
$42,942
612,544
kWh
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs