| Assessment Year | 1992 |
|---|---|
| Principal Product | BEEF, PORK, POULTRY PROD |
| NAICS |
n/a
|
| SIC | 2011: Meat Packing Plants |
| Sales Range | $10 M to 50M |
| # of Employees | 110 |
| Plant Area |
n/a
|
| Annual Production | 10,000,000
lb
|
| Production Hrs. Annual | 2,210
hrs
|
| Location (State) | Florida |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $117,903 | 1,807,737 |
kWh
|
$0.065 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $29,083 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings |
|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $332 | $282 |
$332
4,982
kWh
|
|
| 02 | 2.7144: Install spectral reflectors / delamp | $3,496 | $12,120 |
$3,496
53,927
kWh
|
|
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $477 | $1,603 |
$477
7,327
kWh
|
|
| 04 | 2.4133: Use most efficient type of electric motors | $21 | $4,164 |
$21
293
kWh
|
|
| 05 | 2.4221: Install compressor air intakes in coolest locations | $29 | $75 |
$29
586
kWh
|
|
| 06 | 2.2621: Modify refrigeration system to operate at a lower pressure | $24,728 | $42,000 |
$24,728
380,422
kWh
|
|
| TOTAL RECOMMENDED | $29,083 | $60,244 |
$29,083
447,537
kWh
|
||
| TOTAL IMPLEMENTED | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs