| Assessment Year | 2026 |
|---|---|
| Principal Product | Soaps, body washes, fragrances |
| NAICS | 325620: Toilet Preparation Manufacturing |
| SIC | 2844: Perfumes, Cosmetics, and Other Toilet Preparations |
| Sales Range | $100 M to 500M |
| # of Employees | 500 |
| Plant Area |
394,000
ft2
|
| Annual Production | 75,799
ton
|
| Production Hrs. Annual | 6,936
hrs
|
| Location (State) | Ohio |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $868,240 | 8,495,310 |
kWh
|
$0.10 | |
| Electricity Demand | $111,519 | 15,909 |
kW-mo/yr
|
$7.01 | |
| Electricity Fees | $226 | - |
|
- | |
| Natural Gas | $390,013 | 46,875 |
MMBtu
|
$8.32 | |
| Waste Disposal Costs | |||||
| Water Usage | $290,463 | 56,194 |
Tgal
|
$5.17 | |
| Water Disposal | $1,109,949 | 37,346 |
Tgal
|
$29.72 | |
| Other Liquid (non-haz) | $70,144 | 1 |
gal
|
$70,144.00 | |
| TOTAL YEARLY COSTS | $2,840,554 | ||||
| RECOMMENDED SAVINGS* | $139,001 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | - | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,512 | - |
$1,352
13,228
kWh
|
$160
-
kW-mo/yr
|
- | - | |
| 02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $49,468 | $17,400 |
$44,220
432,678
kWh
|
$5,248
-
kW-mo/yr
|
- | - | |
| 03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $14,971 | - |
$13,383
130,944
kWh
|
$1,588
-
kW-mo/yr
|
- | - | |
| 04 | 2.4221: Install compressor air intakes in coolest locations | $11,470 | $4,800 |
$10,223
100,026
kWh
|
$1,247
-
kW-mo/yr
|
- | - | |
| 05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $16,401 | $13,776 |
$11,194
109,533
kWh
|
$1,328
-
kW-mo/yr
|
- | $3,879 | |
| 06 | 2.7241: Install outside air damper / economizer on hvac unit | $3,410 | $2,873 |
$3,410
33,362
kWh
|
- | - | - | |
| 07 | 2.2414: Use waste heat from hot flue gases to preheat | $18,828 | $40,950 |
$(-1,057.0)
(-10,344)
kWh
|
$(-125.0)
-
kW-mo/yr
|
$20,010
-
MMBtu
|
- | |
| 08 | 2.1233: Analyze flue gas for proper air/fuel ratio | $14,941 | - | - | - |
$14,941
-
MMBtu
|
- | |
| 09 | 2.2113: Repair or replace steam traps | $8,000 | $2,880 | - | - |
$8,000
-
MMBtu
|
- | |
| TOTAL RECOMMENDED | $139,001 | $82,679 |
$82,725
809,427
kWh
|
$9,446
-
kW-mo/yr
|
$42,951
-
MMBtu
|
$3,879 | ||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs