| Assessment Year | 2026 |
|---|---|
| Principal Product | Custom Metal packaging and decorative metal products |
| NAICS | 332812: Metal Coating, Engraving (except Jewelry and Silverware), and Allied Services to Manufacturers |
| SIC | 3479: Coating, Engraving, and Allied Services, Not Elsewhere Classified |
| Sales Range | $5 M to 10M |
| # of Employees | 75 |
| Plant Area |
250,000
ft2
|
| Annual Production | 5,164,886
units
|
| Production Hrs. Annual | 3,760
hrs
|
| Location (State) | Ohio |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $216,021 | 4,835,700 |
kWh
|
$0.045 | |
| Electricity Demand | $383,708 | 19,557 |
kW-mo/yr
|
$19.62 | |
| Electricity Fees | $7,200 | - |
|
- | |
| Natural Gas | $233,479 | 45,848 |
MMBtu
|
$5.09 | |
| Waste Disposal Costs | |||||
| Water Usage | $7,617 | 356 |
Tgal
|
$21.40 | |
| Water Disposal | $5,978 | 356 |
Tgal
|
$16.79 | |
| TOTAL YEARLY COSTS | $854,003 | ||||
| RECOMMENDED SAVINGS* | $74,013 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | - | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Administrative Changes Savings |
|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $8,028 | $1,000 |
$3,344
74,799
kWh
|
$4,684
-
kW-mo/yr
|
- | - | - | |
| 02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $4,391 | - |
$1,829
40,914
kWh
|
$2,562
-
kW-mo/yr
|
- | - | - | |
| 03 | 2.4221: Install compressor air intakes in coolest locations | $3,681 | $4,800 |
$1,506
33,682
kWh
|
$2,175
-
kW-mo/yr
|
- | - | - | |
| 04 | 2.2443: Re-use or recycle hot or cold process exhaust air | $38,983 | $15,000 | - | - | - |
$38,983
-
MMBtu
|
- | |
| 05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $11,899 | $20,626 |
$4,650
104,017
kWh
|
$6,513
-
kW-mo/yr
|
- | - | $736 | |
| 06 | 2.3212: Optimize plant power factor | $7,031 | $18,291 | - | - | $7,031 | - | - | |
| TOTAL RECOMMENDED | $74,013 | $59,717 |
$11,329
253,412
kWh
|
$15,934
-
kW-mo/yr
|
$7,031 |
$38,983
-
MMBtu
|
$736 | ||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Administrative Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs