| Assessment Year | 2024 |
|---|---|
| Principal Product | Metal Products |
| NAICS | 332999: All Other Miscellaneous Fabricated Metal Product Manufacturing |
| SIC | 3499: Fabricated Metal Products, Not Elsewhere Classified |
| Sales Range | $100 M to 500M |
| # of Employees | 250 |
| Plant Area |
380,000
ft2
|
| Annual Production | 1
units
|
| Production Hrs. Annual | 8,568
hrs
|
| Location (State) | Ohio |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $1,000,098 | 17,012,800 |
kWh
|
$0.059 | |
| Electricity Demand | $498,961 | 33,897 |
kW-mo/yr
|
$14.72 | |
| Electricity Fees | $8,042 | - |
|
- | |
| Natural Gas | $119,315 | 18,771 |
MMBtu
|
$6.36 | |
| Waste Disposal Costs | |||||
| Water Usage | $45,861 | 9,219 |
Tgal
|
$4.97 | |
| Water Disposal | $73,497 | 9,219 |
Tgal
|
$7.97 | |
| Other Liquid (non-haz) | $31,842 | 1 |
gal
|
$31,842.00 | |
| TOTAL YEARLY COSTS | $1,777,616 | ||||
| RECOMMENDED SAVINGS* | $134,164 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | $85,434 | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Water Disposal Savings |
|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $792 | - |
$586
9,968
kWh
|
$206
-
kW-mo/yr
|
- | - | - | |
| 02 | 2.5123: Reduce fluid flow rates | $29,869 | $3,076 |
$29,869
507,970
kWh
|
- | - | - | - | |
| 03 | 2.7241: Install outside air damper / economizer on hvac unit | $55,362 | $1,000 |
$55,362
941,530
kWh
|
- | - | - | - | |
| 04 | 2.1233: Analyze flue gas for proper air/fuel ratio | $1,442 | - | - | - | - |
$1,442
-
MMBtu
|
- | |
| 05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $16,187 | $7,000 |
$11,985
203,825
kWh
|
$4,202
-
kW-mo/yr
|
- | - | - | |
| 06 | 2.4221: Install compressor air intakes in coolest locations | $12,481 | $730 |
$9,294
158,069
kWh
|
$3,187
-
kW-mo/yr
|
- | - | - | |
| 07 | 2.4239: Eliminate or reduce compressed air usage | $7,626 | $7,875 |
$161
2,730
kWh
|
$7,465
-
kW-mo/yr
|
- | - | - | |
| 08 | 2.4235: Remove or close off unneeded compressed air lines | $3,404 | - |
$3,404
57,883
kWh
|
- | - | - | - | |
| 09 | 2.3212: Optimize plant power factor | $6,380 | $17,600 | - | - | $6,380 | - | - | |
| 10 | 3.4116: Meter recycled water (to reduce sewer charges) | $621 | $16,000 | - | - | - | - |
$621
-
Tgal
|
|
| TOTAL RECOMMENDED | $134,164 | $53,281 |
$110,661
1,881,975
kWh
|
$15,060
-
kW-mo/yr
|
$6,380 |
$1,442
-
MMBtu
|
$621
-
Tgal
|
||
| TOTAL IMPLEMENTED | $85,434 | $31,875 |
$71,498
1,215,936
kWh
|
$11,873
-
kW-mo/yr
|
- |
$1,442
-
MMBtu
|
$621
-
Tgal
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Water Disposal Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs