| Assessment Year | 2022 |
|---|---|
| Principal Product | Painted Glassware |
| NAICS | 327215: Glass Product Manufacturing Made of Purchased Glass |
| SIC | 3231: Glass Products, Made of Purchased Glass |
| Sales Range | $10 M to 50M |
| # of Employees | 120 |
| Plant Area |
98,000
ft2
|
| Annual Production | 23,000,000
units
|
| Production Hrs. Annual | 6,000
hrs
|
| Location (State) | Ohio |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $79,009 | 1,760,710 |
kWh
|
$0.045 |
| Electricity Demand | $25,447 | 3,473 |
kW-mo/yr
|
$7.33 |
| Electricity Fees | $309 | - |
|
- |
| Natural Gas | $104,913 | 21,277 |
MMBtu
|
$4.93 |
| TOTAL YEARLY COSTS | $209,678 | |||
| RECOMMENDED SAVINGS* | $66,136 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $19,604 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.6212: Turn off equipment during breaks, reduce operating time | $5,459 | - |
$5,459
121,652
kWh
|
- | - | - | |
| 02 | 2.6212: Turn off equipment during breaks, reduce operating time | $3,378 | - |
$3,378
75,292
kWh
|
- | - | - | |
| 03 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,323 | - |
$1,007
22,436
kWh
|
$316
-
kW-mo/yr
|
- | - | |
| 04 | 2.1123: Install automatic stack damper | $4,890 | $2,000 | - | - |
$4,890
-
MMBtu
|
- | |
| 05 | 2.4145: Install isolation transformer on adjustable frequency drive | $26,903 | $30,000 | - | - |
$26,903
-
MMBtu
|
- | |
| 06 | 2.4221: Install compressor air intakes in coolest locations | $657 | $1,500 |
$537
11,963
kWh
|
$120
-
kW-mo/yr
|
- | - | |
| 07 | 2.4239: Eliminate or reduce compressed air usage | $5,245 | - |
$5,245
116,900
kWh
|
- | - | - | |
| 08 | 2.4239: Eliminate or reduce compressed air usage | $16,275 | $14,400 |
$12,384
276,004
kWh
|
$3,891
-
kW-mo/yr
|
- | - | |
| 09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,006 | $6,975 |
$1,081
24,093
kWh
|
$741
-
kW-mo/yr
|
- | $184 | |
| TOTAL RECOMMENDED | $66,136 | $54,875 |
$29,091
648,340
kWh
|
$5,068
-
kW-mo/yr
|
$31,793
-
MMBtu
|
$184 | ||
| TOTAL IMPLEMENTED | $19,604 | $21,375 |
$14,472
322,533
kWh
|
$4,948
-
kW-mo/yr
|
- | $184 | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs