Assessment Year | 2021 |
---|---|
Principal Product | Industrial Valves |
NAICS | 332911: Industrial Valve Manufacturing |
SIC | 3491: Industrial Valves |
Sales Range | $50 M to 100M |
# of Employees | 150 |
Plant Area |
40,000
ft2
|
Annual Production | 227,000,000
ton
|
Production Hrs. Annual | 5,964
hrs
|
Location (State) | Ohio |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $203,626 | 4,121,982 |
kWh
|
$0.049 | |
Electricity Demand | $48,399 | 8,532 |
kW-mo/yr
|
$5.67 | |
Electricity Fees | $70,692 | - |
|
- | |
Natural Gas | $34,211 | 7,985 |
MMBtu
|
$4.28 | |
Waste Disposal Costs | |||||
Water Usage | $3,362 | 697 |
Tgal
|
$4.82 | |
Water Disposal | $6,778 | 653 |
Tgal
|
$10.38 | |
TOTAL YEARLY COSTS | $367,068 | ||||
RECOMMENDED SAVINGS* | $57,030 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.6218: Turn off equipment when not in use | $9,882 | - |
$8,539
172,845
kWh
|
$1,343
-
kW-mo/yr
|
- | - | |
02 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $218 | - |
$125
2,521
kWh
|
$93
-
kW-mo/yr
|
- | - | |
03 | 2.7491: Insulate glazing, walls, ceilings, and roofs | $163 | - | - | - |
$163
-
MMBtu
|
- | |
04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $33,329 | $14,912 |
$28,801
583,012
kWh
|
$4,528
-
kW-mo/yr
|
- | - | |
05 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,341 | - |
$1,023
20,676
kWh
|
$318
-
kW-mo/yr
|
- | - | |
06 | 2.4221: Install compressor air intakes in coolest locations | $1,275 | $3,000 |
$970
19,638
kWh
|
$305
-
kW-mo/yr
|
- | - | |
07 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $605 | $340 |
$1,282
25,952
kWh
|
$403
-
kW-mo/yr
|
- | $(-1,080.0) | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,553 | $5,220 |
$932
18,860
kWh
|
$519
-
kW-mo/yr
|
- | $102 | |
09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $936 | $1,600 |
$736
14,892
kWh
|
$231
-
kW-mo/yr
|
- | $(-31.0) | |
10 | 2.7135: Install occupancy sensors | $904 | $560 |
$480
9,709
kWh
|
$106
-
kW-mo/yr
|
- | $318 | |
11 | 2.1224: Replace boiler | $6,824 | $18,600 | - | - |
$6,824
-
MMBtu
|
- | |
TOTAL RECOMMENDED | $57,030 | $44,232 |
$42,888
868,105
kWh
|
$7,846
-
kW-mo/yr
|
$6,987
-
MMBtu
|
$(-691.0) | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs