Assessment Year | 2017 |
---|---|
Principal Product | Sandwiches |
NAICS | 311611: Animal (except Poultry) Slaughtering |
SIC | 2011: Meat Packing Plants |
Sales Range | $10 M to 50M |
# of Employees | 96 |
Plant Area |
77,546
ft2
|
Annual Production | 58,000,000
units
|
Production Hrs. Annual | 8,400
hrs
|
Location (State) | Ohio |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $367,118 | 4,400,724 |
kWh
|
$0.083 | |
Electricity Demand | $26,979 | 8,592 |
kW-mo/yr
|
$3.14 | |
Electricity Fees | $2,423 | - |
|
- | |
Natural Gas | $61,997 | 11,408 |
MMBtu
|
$5.43 | |
Waste Disposal Costs | |||||
Water Usage | $22,723 | 6,903 |
Tgal
|
$3.29 | |
Water Disposal | $25,119 | 6,903 |
Tgal
|
$3.64 | |
TOTAL YEARLY COSTS | $506,359 | ||||
RECOMMENDED SAVINGS* | $126,729 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $97,250 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Usage Savings | Water Disposal Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.6212: Turn off equipment during breaks, reduce operating time | $6,857 | - |
$6,857
94,050
kWh
|
- | - | - | - | - | |
02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $303 | - |
$280
3,840
kWh
|
$23
-
kW-mo/yr
|
- | - | - | - | |
03 | 3.2172: Use automatic cleaning equipment | $15,770 | - |
$(-1,208.0)
(-16,575)
kWh
|
$(-294.0)
-
kW-mo/yr
|
$6,163
-
MMBtu
|
$11,109
-
Tgal
|
- | - | |
04 | 3.4116: Meter recycled water (to reduce sewer charges) | $6,437 | $700 | - | - | - | - |
$6,437
-
Tgal
|
- | |
05 | 2.2523: Reduce infiltration to refrigerated areas; isolate hot equipment from refrigerated areas | $26,366 | $2,000 |
$24,897
341,480
kWh
|
$1,469
-
kW-mo/yr
|
- | - | - | - | |
06 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $14,440 | $80,000 |
$14,134
193,859
kWh
|
$306
-
kW-mo/yr
|
- | - | - | - | |
07 | 2.2621: Modify refrigeration system to operate at a lower pressure | $4,537 | $10,000 |
$4,284
58,754
kWh
|
$253
-
kW-mo/yr
|
- | - | - | - | |
08 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $3,342 | $200 |
$3,156
43,283
kWh
|
$186
-
kW-mo/yr
|
- | - | - | - | |
09 | 2.7264: Interlock heating and air conditioning systems to prevent simultaneous operation | $5,101 | - |
$3,099
42,505
kWh
|
$183
-
kW-mo/yr
|
$1,819
-
MMBtu
|
- | - | - | |
10 | 2.6212: Turn off equipment during breaks, reduce operating time | $41,935 | $20,000 |
$39,599
543,120
kWh
|
$2,336
-
kW-mo/yr
|
- | - | - | - | |
11 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $560 | $300 |
$560
7,677
kWh
|
- | - | - | - | - | |
12 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,081 | $1,230 |
$1,057
14,510
kWh
|
$56
-
kW-mo/yr
|
- | - | - | $(-32.0) | |
TOTAL RECOMMENDED | $126,729 | $114,430 |
$96,715
1,326,503
kWh
|
$4,518
-
kW-mo/yr
|
$7,982
-
MMBtu
|
$11,109
-
Tgal
|
$6,437
-
Tgal
|
$(-32.0) | ||
TOTAL IMPLEMENTED | $97,250 | $24,230 |
$68,004
932,717
kWh
|
$3,750
-
kW-mo/yr
|
$7,982
-
MMBtu
|
$11,109
-
Tgal
|
$6,437
-
Tgal
|
$(-32.0) | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Usage Savings | Water Disposal Savings | Personnel Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs