Assessment Year | 2014 |
---|---|
Principal Product | Turf Building, Commercial Fertilizer, EZSeed |
NAICS | 325314: Fertilizer (Mixing Only) Manufacturing |
SIC | 2875: Fertilizers, Mixing Only |
Sales Range | $100 M to 500M |
# of Employees | 265 |
Plant Area |
1,800,000
ft2
|
Annual Production | 584,596,011
lb
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Ohio |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $980,373 | 18,706,510 |
kWh
|
$0.052 |
Electricity Demand | $190,548 | 40,200 |
kW-mo/yr
|
$4.74 |
Natural Gas | $496,519 | 84,462 |
MMBtu
|
$5.88 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $404,866 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $112,398 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $2,544 | - |
$2,156
42,609
kWh
|
$388
-
kW-mo/yr
|
- | - | - | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $10,620 | $1,000 |
$10,015
197,967
kWh
|
$1,805
-
kW-mo/yr
|
- | - | $(-1,200.0) | |
03 | 2.4221: Install compressor air intakes in coolest locations | $5,866 | $8,000 |
$4,970
98,250
kWh
|
$896
-
kW-mo/yr
|
- | - | - | |
04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $4,693 | - |
$3,977
78,624
kWh
|
$716
-
kW-mo/yr
|
- | - | - | |
05 | 2.4113: Install motor voltage controller on lightly loaded motors | $14,978 | $20,079 |
$12,691
250,850
kWh
|
$2,287
-
kW-mo/yr
|
- | - | - | |
06 | 2.1221: Replace obsolete burners with more efficient ones | $74,000 | $124,534 | - | - |
$74,000
-
MMBtu
|
- | - | |
07 | 2.2414: Use waste heat from hot flue gases to preheat | $18,375 | $7,000 | - | - |
$18,375
-
MMBtu
|
- | - | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $10,256 | $47,188 |
$7,672
151,645
kWh
|
$2,584
-
kW-mo/yr
|
- | - | - | |
09 | 2.7134: Use photocell controls | $732 | $1,440 |
$732
14,475
kWh
|
- | - | - | - | |
10 | 3.3123: Use decanting, flotation to remove contaminants | $262,802 | $80,000 |
$(-1,630.0)
(-32,211)
kWh
|
$(-768.0)
-
kW-mo/yr
|
- |
$265,200
-
Tgal
|
- | |
TOTAL RECOMMENDED | $404,866 | $289,241 |
$40,583
802,209
kWh
|
$7,908
-
kW-mo/yr
|
$92,375
-
MMBtu
|
$265,200
-
Tgal
|
$(-1,200.0) | ||
TOTAL IMPLEMENTED | $112,398 | $192,801 |
$32,534
643,071
kWh
|
$7,064
-
kW-mo/yr
|
$74,000
-
MMBtu
|
- | $(-1,200.0) | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs