Assessment Year | 2014 |
---|---|
Principal Product | Blow Molded Plastics |
NAICS | 326121: Unlaminated Plastics Profile Shape Manufacturing |
SIC | 3089: Plastics Products, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 284 |
Plant Area |
81,182
ft2
|
Annual Production | 5,250,000
pieces
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Ohio |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $670,583 | 11,725,533 |
kWh
|
$0.057 |
Electricity Demand | $134,326 | 19,272 |
kW-mo/yr
|
$6.97 |
Electricity Fees | $28,254 | - |
|
- |
Natural Gas | $31,565 | 4,002 |
MMBtu
|
$7.89 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $159,854 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $158,602 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4131: Size electric motors for peak operating efficiency | $72,083 | - |
$61,770
1,080,084
kWh
|
$10,313
-
kW-mo/yr
|
- | - | |
02 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $21,208 | - |
$18,174
317,776
kWh
|
$3,034
-
kW-mo/yr
|
- | - | |
03 | 2.7241: Install outside air damper / economizer on hvac unit | $48,509 | $7,500 |
$41,835
731,503
kWh
|
$6,674
-
kW-mo/yr
|
- | - | |
04 | 2.7442: Keep doors and windows shut when not on use | $2,209 | - | - | - |
$2,209
-
MMBtu
|
- | |
05 | 2.7131: Add area lighting switches | $1,613 | $1,575 |
$1,154
20,183
kWh
|
$193
-
kW-mo/yr
|
- | $266 | |
06 | 2.7135: Install occupancy sensors | $1,252 | $2,900 |
$1,177
20,590
kWh
|
- | - | $75 | |
07 | 2.7121: Utilize daylight whenever possible in lieu of artificial light | $249 | $510 |
$249
4,363
kWh
|
- | - | - | |
08 | 2.2622: Replace existing chiller with high efficiency model | $6,823 | $16,000 |
$5,847
102,241
kWh
|
$976
-
kW-mo/yr
|
- | - | |
09 | 2.4131: Size electric motors for peak operating efficiency | $3,388 | $800 |
$2,903
50,761
kWh
|
$485
-
kW-mo/yr
|
- | - | |
10 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $2,520 | $4,275 |
$2,520
44,067
kWh
|
- | - | - | |
TOTAL RECOMMENDED | $159,854 | $33,560 |
$135,629
2,371,568
kWh
|
$21,675
-
kW-mo/yr
|
$2,209
-
MMBtu
|
$341 | ||
TOTAL IMPLEMENTED | $158,602 | $30,660 |
$134,452
2,350,978
kWh
|
$21,675
-
kW-mo/yr
|
$2,209
-
MMBtu
|
$266 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs