Assessment Year | 2012 |
---|---|
Principal Product | Windows & Entry Doors |
NAICS | 326199: All Other Plastics Product Manufacturing |
SIC | 3089: Plastics Products, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 242 |
Plant Area |
165,000
ft2
|
Annual Production | 86,500
pieces
|
Production Hrs. Annual | 2,080
hrs
|
Location (State) | Ohio |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $133,759 | 2,570,136 |
kWh
|
$0.052 |
Electricity Demand | $168,370 | 10,512 |
kW-mo/yr
|
$16.02 |
Electricity Fees | $536 | - |
|
- |
Natural Gas | $23,544 | 3,080 |
MMBtu
|
$7.64 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $57,929 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $21,745 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.3131: Reschedule plant operations or reduce load to avoid peaks | $4,535 | - |
$(-87.0)
(-1,671)
kWh
|
$4,622
-
kW-mo/yr
|
- | - | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $29,026 | $107,140 |
$12,666
236,858
kWh
|
$15,395
-
kW-mo/yr
|
- | $965 | |
03 | 2.7135: Install occupancy sensors | $1,542 | $1,350 |
$1,542
29,652
kWh
|
- | - | - | |
04 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,282 | - |
$462
8,877
kWh
|
$820
-
kW-mo/yr
|
- | - | |
05 | 2.4224: Upgrade controls on compressors | $2,154 | $380 |
$776
14,914
kWh
|
$1,378
-
kW-mo/yr
|
- | - | |
06 | 2.4221: Install compressor air intakes in coolest locations | $1,591 | $2,000 |
$573
11,009
kWh
|
$1,018
-
kW-mo/yr
|
- | - | |
07 | 2.4224: Upgrade controls on compressors | $682 | $1,000 |
$246
4,722
kWh
|
$436
-
kW-mo/yr
|
- | - | |
08 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,792 | $1,000 |
$429
8,251
kWh
|
$763
-
kW-mo/yr
|
- | $600 | |
09 | 2.2514: Cover open tanks | $1,393 | $800 |
$509
9,807
kWh
|
$884
-
kW-mo/yr
|
- | - | |
10 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $1,355 | $2,415 |
$583
11,220
kWh
|
$1,078
-
kW-mo/yr
|
$(-306.0)
-
MMBtu
|
- | |
11 | 2.7224: Reduce space conditioning during non-working hours | $11,912 | $5,400 | - | - |
$11,912
-
MMBtu
|
- | |
12 | 2.7311: Ventilation system to shut off when room is not in use | $665 | $2,000 |
$175
3,362
kWh
|
- |
$490
-
MMBtu
|
- | |
TOTAL RECOMMENDED | $57,929 | $123,485 |
$17,874
337,001
kWh
|
$26,394
-
kW-mo/yr
|
$12,096
-
MMBtu
|
$1,565 | ||
TOTAL IMPLEMENTED | $21,745 | $8,750 |
$2,592
49,831
kWh
|
$6,641
-
kW-mo/yr
|
$11,912
-
MMBtu
|
$600 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs