ITAC Assessment: UD0843
ITAC logo
ITAC Assessment: UD0843
Grant Funding Opportunity NOW OPEN
Up to $300k at 50% cost share for qualifying* projects.
Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received an ITAC, Onsite Energy/CHP TAP, or qualified equivalent assessment since 2018 can now apply for grants for implementation of assessment recommendations at up to 50% of qualifying* project costs with a maximum of $300,000 per grant.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
Assessment Year 2011
Principal Product Plastic containers
NAICS 326160: Plastics Bottle Manufacturing
SIC 3085: Plastics Bottles
Sales Range $10
M
to 50
M
# of Employees 28
Plant Area 115,000
ft2
Annual Production 23,770,594
pieces
Production Hrs. Annual 6,000
hrs
Location (State) Ohio

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $342,901 6,753,200
kWh
Electricity Demand $262,049 14,304
kW-mo/yr
Natural Gas $51,704 4,250
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $46,399 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $12,567

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Personnel Changes Savings
01 2.7142: Utilize higher efficiency lamps and/or ballasts $29,573 $18,563 $17,150
347,580
kWh
$12,791
-
kW-mo/yr
$(-368.0)
02 2.7111: Reduce illumination to minimum necessary levels $2,770 - $2,770
44,150
kWh
- -
03 2.7142: Utilize higher efficiency lamps and/or ballasts $143 $407 $77
1,560
kWh
$57
-
kW-mo/yr
$9
04 2.4111: Utilize energy-efficient belts and other improved mechanisms $2,904 $5,808 $2,904
58,860
kWh
- -
05 2.4146: Use adjustable frequency drive or multiple speed motors on existing system $2,289 $4,698 $1,311
26,568
kWh
$978
-
kW-mo/yr
-
06 2.4231: Reduce the pressure of compressed air to the minimum required $1,854 - $1,062
21,528
kWh
$792
-
kW-mo/yr
-
07 2.4221: Install compressor air intakes in coolest locations $1,212 $5,000 $694
14,068
kWh
$518
-
kW-mo/yr
-
08 2.6231: Utilize controls to operate equipment only when needed $509 - $509
10,320
kWh
- -
09 2.4111: Utilize energy-efficient belts and other improved mechanisms $5,145 $650 $5,145
104,273
kWh
- -
TOTAL RECOMMENDED $46,399 $35,126 $31,622
628,907
kWh
$15,136
-
kW-mo/yr
$(-359.0)
TOTAL IMPLEMENTED $12,567 $5,348 $10,797
206,839
kWh
$1,770
-
kW-mo/yr
-
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Personnel Changes Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs