| Assessment Year | 2008 |
|---|---|
| Principal Product | Printing |
| NAICS | 323111: Commercial Printing (except Screen and Books) |
| SIC | 2752: Commercial Printing, Lithographic |
| Sales Range | $50 M to 100M |
| # of Employees | 400 |
| Plant Area |
200,200
ft2
|
| Annual Production | 350,094,386
units
|
| Production Hrs. Annual | 7,200
hrs
|
| Location (State) | Kentucky |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $996,489 | 14,696,896 |
kWh
|
$0.068 |
| Natural Gas | $271,238 | 25,311 |
MMBtu
|
$10.72 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $121,828 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $5,422 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.2437: Recover waste heat from equipment | $77,393 | $80,770 | - | - |
$77,393
-
MMBtu
|
|
| 02 | 2.4322: Use or replace with energy efficient substitutes | $10,780 | $12,000 |
$6,912
172,800
kWh
|
$3,868
-
kW-mo/yr
|
- | |
| 03 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $6,222 | $22,560 |
$6,222
89,549
kWh
|
- | - | |
| 04 | 2.2533: Replace air curtain doors with solid doors | $5,905 | $18,000 |
$126
3,139
kWh
|
$59
-
kW-mo/yr
|
$5,720
-
MMBtu
|
|
| 05 | 2.4224: Upgrade controls on compressors | $3,783 | - |
$2,333
58,320
kWh
|
$1,450
-
kW-mo/yr
|
- | |
| 06 | 2.6218: Turn off equipment when not in use | $3,431 | $6,000 |
$3,431
85,787
kWh
|
- | - | |
| 07 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $2,176 | - |
$1,395
34,876
kWh
|
$781
-
kW-mo/yr
|
- | |
| 08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,563 | $6,075 |
$1,002
25,056
kWh
|
$561
-
kW-mo/yr
|
- | |
| 09 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $6,692 | $5,992 |
$4,291
107,280
kWh
|
$2,401
-
kW-mo/yr
|
- | |
| 10 | 2.7135: Install occupancy sensors | $1,683 | $4,305 |
$1,683
37,739
kWh
|
- | - | |
| 11 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,302 | - |
$835
20,880
kWh
|
$467
-
kW-mo/yr
|
- | |
| 12 | 2.4322: Use or replace with energy efficient substitutes | $853 | $310 |
$547
13,680
kWh
|
$306
-
kW-mo/yr
|
- | |
| 13 | 2.4231: Reduce the pressure of compressed air to the minimum required | $45 | - |
$29
720
kWh
|
$16
-
kW-mo/yr
|
- | |
| TOTAL RECOMMENDED | $121,828 | $156,012 |
$28,806
649,826
kWh
|
$9,909
-
kW-mo/yr
|
$83,113
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $5,422 | $10,380 |
$4,080
97,671
kWh
|
$1,342
-
kW-mo/yr
|
- | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs