Assessment Year | 2007 |
---|---|
Principal Product | Wood Office Furniture |
NAICS | 337211: Wood Office Furniture Manufacturing |
SIC | 2521: Wood Office Furniture |
Sales Range | $100 M to 500M |
# of Employees | 707 |
Plant Area |
1,196,000
ft2
|
Annual Production | 260,000
pieces
|
Production Hrs. Annual | 2,450
hrs
|
Location (State) | Indiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $909,559 | 13,647,625 |
kWh
|
$0.067 |
Natural Gas | $631,944 | 64,778 |
MMBtu
|
$9.76 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $273,822 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $201,771 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 4.454: Modify startup/shutdown times | $144,431 | - |
$7,231
109,564
kWh
|
- | - | $137,200 | - | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $37,082 | $161,076 |
$33,617
509,355
kWh
|
$3,465
-
kW-mo/yr
|
- | - | - | |
03 | 2.7314: Reduce ventilation air | $19,800 | $1,590 |
$8,659
131,198
kWh
|
$893
-
kW-mo/yr
|
$10,248
-
MMBtu
|
- | - | |
04 | 2.7311: Ventilation system to shut off when room is not in use | $14,325 | $3,260 |
$3,218
48,755
kWh
|
- |
$11,107
-
MMBtu
|
- | - | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $13,452 | $71,033 |
$11,931
180,776
kWh
|
$778
-
kW-mo/yr
|
- | - | $743 | |
06 | 2.4224: Upgrade controls on compressors | $11,132 | $25,500 |
$10,187
154,350
kWh
|
$945
-
kW-mo/yr
|
- | - | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $10,540 | $58,765 |
$8,033
121,716
kWh
|
$828
-
kW-mo/yr
|
- | - | $1,679 | |
08 | 2.4224: Upgrade controls on compressors | $7,421 | $17,000 |
$6,791
102,900
kWh
|
$630
-
kW-mo/yr
|
- | - | - | |
09 | 2.4231: Reduce the pressure of compressed air to the minimum required | $7,068 | - |
$6,468
98,000
kWh
|
$600
-
kW-mo/yr
|
- | - | - | |
10 | 2.7132: Install timers on light switches in little used areas | $5,744 | $600 |
$5,744
87,028
kWh
|
- | - | - | - | |
11 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,297 | $3,275 |
$2,102
31,850
kWh
|
$195
-
kW-mo/yr
|
- | - | - | |
12 | 2.4322: Use or replace with energy efficient substitutes | $530 | $930 |
$485
7,350
kWh
|
$45
-
kW-mo/yr
|
- | - | - | |
TOTAL RECOMMENDED | $273,822 | $343,029 |
$104,466
1,582,842
kWh
|
$8,379
-
kW-mo/yr
|
$21,355
-
MMBtu
|
$137,200 | $2,422 | ||
TOTAL IMPLEMENTED | $201,771 | $240,116 |
$57,774
875,385
kWh
|
$5,118
-
kW-mo/yr
|
- | $137,200 | $1,679 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs