Assessment Year 2004
Principal Product Flat-rolled steel
NAICS 331221: Rolled Steel Shape Manufacturing
SIC 3316: Cold-Rolled Steel Sheet, Strip, and Bars
Sales Range $50
M
to 100
M
# of Employees 143
Plant Area 308,000
ft2
Annual Production 128
ton
Production Hrs. Annual 4,860
hrs
Location (State) Ohio

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $135,720 11,781,600
kWh
Electricity Demand $98,297 11,148
kW-mo/yr
Other Energy $85,463 7,431
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $65,828 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $14,636

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Electricity Fees Savings Other Energy Savings Personnel Changes Savings
01 3.4151: Minimize water usage $20,840 $1,380 $140
4,500
kWh
- - $20,700
-
MMBtu
-
02 2.7142: Utilize higher efficiency lamps and/or ballasts $18,415 $18,250 $(-15.0)
(-470)
kWh
- - $21,850
-
MMBtu
$(-3,420.0)
03 2.4226: Use / purchase optimum sized compressor $6,885 $630 $4,135
133,380
kWh
$2,750
-
kW-mo/yr
- - -
04 2.3212: Optimize plant power factor $5,450 $8,600 - - $5,450 - -
05 2.4146: Use adjustable frequency drive or multiple speed motors on existing system $5,290 $16,271 $3,840
123,864
kWh
$1,450
-
kW-mo/yr
- - -
06 2.7122: Disconnect ballasts $4,541 $68 $2,669
86,112
kWh
$1,872
-
kW-mo/yr
- - -
07 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $1,530 $630 $920
29,640
kWh
$610
-
kW-mo/yr
- - -
08 2.4222: Install adequate dryers on air lines to eliminate blowdown $1,020 - $610
19,760
kWh
$410
-
kW-mo/yr
- - -
09 2.7134: Use photocell controls $890 $220 $890
28,707
kWh
- - - -
10 2.7111: Reduce illumination to minimum necessary levels $790 - $464
14,976
kWh
$326
-
kW-mo/yr
- - -
11 2.5123: Reduce fluid flow rates $177 - $104
3,370
kWh
$73
-
kW-mo/yr
- - -
TOTAL RECOMMENDED $65,828 $46,049 $13,757
443,839
kWh
$7,491
-
kW-mo/yr
$5,450 $42,550
-
MMBtu
$(-3,420.0)
TOTAL IMPLEMENTED $14,636 $1,548 $9,078
292,815
kWh
$5,558
-
kW-mo/yr
- - -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Electricity Fees Savings Other Energy Savings Personnel Changes Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs