| Assessment Year | 2001 |
|---|---|
| Principal Product | Injection molded thermoplastics |
| NAICS |
n/a
|
| SIC | 3089: Plastics Products, Not Elsewhere Classified |
| Sales Range | $10 M to 50M |
| # of Employees | 195 |
| Plant Area |
155,000
ft2
|
| Annual Production | 19,200,000
pieces
|
| Production Hrs. Annual | 5,760
hrs
|
| Location (State) | Ohio |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $243,482 | 7,901,880 |
kWh
|
$0.031 |
| Electricity Demand | $262,848 | 17,736 |
kW-mo/yr
|
$14.82 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $75,510 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $53,966 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Water Disposal Savings |
|---|---|---|---|---|---|---|---|
| 01 | 3.4111: Use closed cycle process to minimize waste water production | $25,095 | $6,000 |
$11,935
426,240
kWh
|
$13,160
-
kW-mo/yr
|
- | |
| 02 | 2.6231: Utilize controls to operate equipment only when needed | $17,974 | $3,000 |
$8,548
305,280
kWh
|
$9,426
-
kW-mo/yr
|
- | |
| 03 | 2.2511: Insulate bare equipment | $10,072 | $1,560 |
$4,790
171,072
kWh
|
$5,282
-
kW-mo/yr
|
- | |
| 04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $5,223 | $4,000 |
$2,484
88,704
kWh
|
$2,739
-
kW-mo/yr
|
- | |
| 05 | 3.4116: Meter recycled water (to reduce sewer charges) | $4,373 | $600 | - | - |
$4,373
-
Tgal
|
|
| 06 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $4,155 | $5,550 |
$1,976
70,560
kWh
|
$2,179
-
kW-mo/yr
|
- | |
| 07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,150 | $1,750 |
$2,016
72,000
kWh
|
$2,134
-
kW-mo/yr
|
- | |
| 08 | 2.4226: Use / purchase optimum sized compressor | $2,374 | - |
$1,129
40,320
kWh
|
$1,245
-
kW-mo/yr
|
- | |
| 09 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $2,094 | $180 |
$1,258
44,928
kWh
|
$836
-
kW-mo/yr
|
- | |
| TOTAL RECOMMENDED | $75,510 | $22,640 |
$34,136
1,219,104
kWh
|
$37,001
-
kW-mo/yr
|
$4,373
-
Tgal
|
||
| TOTAL IMPLEMENTED | $53,966 | $11,350 |
$23,628
843,840
kWh
|
$25,965
-
kW-mo/yr
|
$4,373
-
Tgal
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Water Disposal Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs