| Assessment Year | 1997 |
|---|---|
| Principal Product | Commercial Printing |
| NAICS |
n/a
|
| SIC | 2752: Commercial Printing, Lithographic |
| Sales Range | $10 M to 50M |
| # of Employees | 160 |
| Plant Area |
120,000
ft2
|
| Annual Production | 0
thousand feet
|
| Production Hrs. Annual | 6,000
hrs
|
| Location (State) | Ohio |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $54,187 | 3,151,231 |
kWh
|
$0.017 |
| Electricity Demand | $142,865 | 17,232 |
kW-mo/yr
|
$8.29 |
| Natural Gas | $4,927 | 786 |
MMBtu
|
$6.27 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $25,103 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $25,103 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Administrative Changes Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.3212: Optimize plant power factor | $14,725 | $15,000 | - |
$14,725
-
kW-mo/yr
|
- | - | |
| 02 | 2.4226: Use / purchase optimum sized compressor | $5,197 | $5,000 |
$1,589
92,321
kWh
|
$3,008
-
kW-mo/yr
|
- | $600 | |
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,181 | $11,751 |
$1,400
81,477
kWh
|
$3,691
-
kW-mo/yr
|
$90 | - | |
| TOTAL RECOMMENDED | $25,103 | $31,751 |
$2,989
173,798
kWh
|
$21,424
-
kW-mo/yr
|
$90 | $600 | ||
| TOTAL IMPLEMENTED | $25,103 | $31,751 |
$2,989
173,798
kWh
|
$21,424
-
kW-mo/yr
|
$90 | $600 | ||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs