Assessment Year | 1997 |
---|---|
Principal Product | acids, chemicals, solvents |
NAICS |
n/a
|
SIC | 2869: Industrial Organic Chemicals, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 160 |
Plant Area |
220,000
ft2
|
Annual Production | 0
units
|
Production Hrs. Annual | 6,000
hrs
|
Location (State) | Ohio |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $94,559 | 4,504,396 |
kWh
|
$0.021 |
Electricity Demand | $151,560 | 9,672 |
kW-mo/yr
|
$15.67 |
Electricity Fees | $3,573 | - |
|
- |
Natural Gas | $148,045 | 40,054 |
MMBtu
|
$3.70 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $18,292 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $9,729 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,109 | $14,870 |
$1,393
66,237
kWh
|
$2,078
-
kW-mo/yr
|
$638 | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $8,524 | $8,150 |
$3,397
161,782
kWh
|
$4,426
-
kW-mo/yr
|
$701 | |
03 | 2.4226: Use / purchase optimum sized compressor | $2,785 | $1,200 |
$2,973
141,559
kWh
|
$(-188.0)
-
kW-mo/yr
|
- | |
04 | 2.4133: Use most efficient type of electric motors | $1,205 | $978 |
$594
28,429
kWh
|
$611
-
kW-mo/yr
|
- | |
05 | 2.4131: Size electric motors for peak operating efficiency | $1,669 | $500 |
$353
16,706
kWh
|
$1,316
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $18,292 | $25,698 |
$8,710
414,713
kWh
|
$8,243
-
kW-mo/yr
|
$1,339 | ||
TOTAL IMPLEMENTED | $9,729 | $9,128 |
$3,991
190,211
kWh
|
$5,037
-
kW-mo/yr
|
$701 |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs