Assessment Year | 1996 |
---|---|
Principal Product | air & hydraulic cylinders |
NAICS |
n/a
|
SIC | 3594: Fluid Power Pumps and Motors |
Sales Range | $10 M to 50M |
# of Employees | 191 |
Plant Area |
132,500
ft2
|
Annual Production | 0
units
|
Production Hrs. Annual | 5,500
hrs
|
Location (State) | Ohio |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $93,331 | 3,084,994 |
kWh
|
$0.030 |
Electricity Demand | $101,288 | 8,364 |
kW-mo/yr
|
$12.11 |
Natural Gas | $28,916 | 6,092 |
MMBtu
|
$4.75 |
Fuel Oil #2 | $9,900 | 1,260 |
MMBtu
|
$7.86 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $43,211 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $43,211 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.3212: Optimize plant power factor | $11,388 | $8,000 | - |
$11,388
-
kW-mo/yr
|
- | - | - | |
02 | 2.4226: Use / purchase optimum sized compressor | $1,091 | - |
$718
36,928
kWh
|
- | - | - | $373 | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $15,416 | $31,170 |
$5,865
302,462
kWh
|
$10,332
-
kW-mo/yr
|
$(-1,616.0)
-
MMBtu
|
$835 | - | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $15,316 | $41,520 |
$5,461
281,653
kWh
|
$9,622
-
kW-mo/yr
|
- | $233 | - | |
TOTAL RECOMMENDED | $43,211 | $80,690 |
$12,044
621,043
kWh
|
$31,342
-
kW-mo/yr
|
$(-1,616.0)
-
MMBtu
|
$1,068 | $373 | ||
TOTAL IMPLEMENTED | $43,211 | $80,690 |
$12,044
621,043
kWh
|
$31,342
-
kW-mo/yr
|
$(-1,616.0)
-
MMBtu
|
$1,068 | $373 |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs