Assessment Year | 1982 |
---|---|
Principal Product | ADHESIVES & SEALANTS |
NAICS |
n/a
|
SIC | 2891: Adhesives and Sealants |
Sales Range | $5 M to 10M |
# of Employees | 70 |
Plant Area |
n/a
|
Annual Production | 6,990,000
Tgal
|
Production Hrs. Annual | 4,000
hrs
|
Location (State) | Ohio |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $123,475 | 1,700,176 |
kWh
|
$0.073 |
Natural Gas | $32,044 | 8,687 |
MMBtu
|
$3.69 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $11,046 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $2,868 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,891 | $396 |
$2,416
38,101
kWh
|
$(-525.0)
-
MMBtu
|
|
02 | 2.1233: Analyze flue gas for proper air/fuel ratio | $1,817 | $400 | - |
$1,817
-
MMBtu
|
|
03 | 2.4221: Install compressor air intakes in coolest locations | $6,054 | $2,800 |
$(-109.0)
(-1,465)
kWh
|
$6,163
-
MMBtu
|
|
04 | 2.7492: Use proper thickness of insulation on building envelope | $1,051 | $5,156 | - |
$1,051
-
MMBtu
|
|
05 | 2.6121: Reduce hot water temperature to the minimum required | $233 | - |
$203
2,931
kWh
|
$30
-
MMBtu
|
|
TOTAL RECOMMENDED | $11,046 | $8,752 |
$2,510
39,567
kWh
|
$8,536
-
MMBtu
|
||
TOTAL IMPLEMENTED | $2,868 | $5,556 | - |
$2,868
-
MMBtu
|
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs