| Assessment Year | 1982 |
|---|---|
| Principal Product | AIRCRAFT ELECTRICAL EQUIPMENT |
| NAICS |
n/a
|
| SIC | 3724: Aircraft Engines and Engine Parts |
| Sales Range | $5 M to 10M |
| # of Employees | 200 |
| Plant Area |
n/a
|
| Annual Production | 0
units
|
| Production Hrs. Annual | 2,200
hrs
|
| Location (State) | Ohio |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $99,402 | 1,982,122 |
kWh
|
$0.050 |
| Natural Gas | $55,786 | 15,067 |
MMBtu
|
$3.70 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $21,255 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $21,255 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|
| 01 | 2.7111: Reduce illumination to minimum necessary levels | $5,309 | $1,610 |
$5,309
76,202
kWh
|
- | |
| 02 | 2.1233: Analyze flue gas for proper air/fuel ratio | $3,870 | $1,450 | - |
$3,870
-
MMBtu
|
|
| 03 | 2.7261: Install timers and/or thermostats | $6,580 | $139 |
$457
9,086
kWh
|
$6,123
-
MMBtu
|
|
| 04 | 2.7492: Use proper thickness of insulation on building envelope | $2,997 | - | - |
$2,997
-
MMBtu
|
|
| 05 | 2.7421: Reduce glazed areas in buildings | $1,633 | $3,410 | - |
$1,633
-
MMBtu
|
|
| 06 | 2.2428: Use flue gases in radiant heater for space heating, ovens, etc | $866 | $4,000 | - |
$866
-
MMBtu
|
|
| TOTAL RECOMMENDED | $21,255 | $10,609 |
$5,766
85,288
kWh
|
$15,489
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $21,255 | $10,609 |
$5,766
85,288
kWh
|
$15,489
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs