Assessment Year | 2024 |
---|---|
Principal Product | Rubber product |
NAICS | 326299: All Other Rubber Product Manufacturing |
SIC | 3069: Fabricated Rubber Products, Not Elsewhere Classified |
Sales Range | $1 M to 5M |
# of Employees | 25 |
Plant Area |
21,000
ft2
|
Annual Production | 20,000,000
lb
|
Production Hrs. Annual | 2,500
hrs
|
Location (State) | Connecticut |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $57,540 | 481,601 |
kWh
|
$0.12 |
Electricity Demand | $53,548 | 2,217 |
kW-mo/yr
|
$24.15 |
Electricity Fees | $9,262 | - |
|
- |
Natural Gas | $31,271 | 2,820 |
MMBtu
|
$11.09 |
TOTAL YEARLY COSTS | $151,620 | |||
RECOMMENDED SAVINGS* | $45,065 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.9114: Use solar heat to make electricty | $17,049 | $134,289 |
$17,049
142,666
kWh
|
- | - | - | |
02 | 2.3141: Use battery storage for demand control | $7,849 | $31,027 |
$(-610.8)
(-5,111)
kWh
|
$8,694
-
kW-mo/yr
|
- | $(-234.5) | |
03 | 2.2136: Install / repair insulation on steam lines | $1,298 | $3,327 | - | - |
$1,298
-
MMBtu
|
- | |
04 | 2.4239: Eliminate or reduce compressed air usage | $2,943 | $1,040 |
$2,363
19,778
kWh
|
$579
-
kW-mo/yr
|
- | - | |
05 | 2.4231: Reduce the pressure of compressed air to the minimum required | $2,261 | $150 |
$1,770
14,809
kWh
|
$491
-
kW-mo/yr
|
- | - | |
06 | 2.6231: Utilize controls to operate equipment only when needed | $4,612 | $30 |
$4,612
38,593
kWh
|
- | - | - | |
07 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $419 | $1,300 |
$328
2,744
kWh
|
$91
-
kW-mo/yr
|
- | - | |
08 | 2.6231: Utilize controls to operate equipment only when needed | $1,934 | $155 |
$1,934
16,187
kWh
|
- | - | - | |
09 | 2.3415: Use a fossil fuel engine to cogenerate electricity or motive power; and utilize heat | $6,701 | $64,088 |
$13,928
116,550
kWh
|
$4,999
-
kW-mo/yr
|
$(-12,225.7)
-
MMBtu
|
- | |
TOTAL RECOMMENDED | $45,065 | $235,406 |
$41,373
346,216
kWh
|
$14,854
-
kW-mo/yr
|
$(-10,928.2)
-
MMBtu
|
$(-234.5) | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs